1565H041 Ed.03
10.2.- Auxiliary relay
This menu is used to configure the different operating options of the auxiliary relay:
Ÿ
AUX relay configuration:
It defines the operation of the auxiliary relay.
ž
Pump down control: It controls the liquid solenoid valve in the stop and start processes with pump
down (See page 21).
ž
Equal compressor state: The auxiliary relay is activated/deactivated by copying the compressor status.
Ÿ
Pump down duration:
It defines the maximum safety time for the stop operation in the pump down mode
(See page 21).
Ÿ
Pump down On delay:
It defines the maximum safety time for the start-up operation in the pump down
mode (See page 21).
10.3.- Access code (password)
It allows protecting the configuration of the unit using a 2 digit code (from 01 to 99). If it is active a code is requested
when you try to access the programming menu. This menu cannot be accessed if a wrong value is entered. The code is
defined using the
Access password
parameter of the
q
menu.
The
Password to Set Point
parameter defines if this code is requested on changing the set point.
10.4.- Return to initial parameters
This function configures all the unit's parameters to its default values, i.e., as it leaves the factory. The date and time data
are not changed.
To return the unit to the initial parameters, select the
q
/
Initial parameters
/Yes in the programming menu.
WARNING:
Any change made in the unit's configuration will be lost.
10.5.- Program version
The
Version and program revision
parameters in the
q
menu allow displaying the firmware version installed in the
unit. Use this information if you have to ask for advice from the technical assistance service.
Auxiliary relay function.