B) Non-Invasive UFLS-NI
This sensor type mounts on the bottom of t
he tank instead of the top, and it doesn’t
require cutting of any holes. Please note the following:
1. The sender must not be mounted closer than 150mm from the center of the sender
to sides of the tank, baffles or other intrusions.
2. Only use on tanks greater than 50mm in depth but no greater than 2000mm deep.
3. Sender must be mounted parallel to the surface of the liquid.
4. You must first clean and clear the mounting surface with sand paper.
5. You must use a coupling agent or gel between the sensor and the surface for
ultrasound conductivity. The coupling agent could be Epoxy glue - make sure to
avoid bubbles or impurity in the gel.
6. The sensor is powered by
the base unit’s sensor port, no external power required.
7. The container thickness should be less than 8mm for best performance.
8. Maximum distance between module and sensor : 450mm
9. Mount below the deepest point of the tank.