LITE THERMOSTATS (AZVAFLITE [C/R])
Lite thermostats incorporate LEDs that detect malfunctioning.
Status LED
blinking purple quickly: Wired Lite Thermostat- Zone module communication error
(AZVAFDAMPERxxC / AZVAFZMRADC / AZVAFZMxxxC)
This incident blocks the control of the zone. To solve this incident check:
1.
Connection: Check the polarity of the connectors of the module and the thermostat.
2.
Wiring: Check that the voltage between the poles (A /-) and (B/-) is about 0.65 Vdc.
3.
Wiring: Verify that the module connection bus-thermostat is not next to low-voltage wiring.
4.
Module: Check the correct operation of the module, for this connect another thermostat and verify that Error 1 does
not appear on the screen.
5.
Restart the zone and re-associate it with the system.
Remember: To reset to factory values of any Lite thermostat, turn up the microswitch 8 and place the thermostat on
the base again. Press on
, the LED will flash green twice when the reset process is completed.
6.
Restart system: If the system is restarted, this error may be displayed in the thermostats at the beginning of the process.
This message should disappear after around 30 seconds.
AZVAFDAMPERxxC / AZVAFZMRADC
Fig. 73
Содержание AZVAF10KPROBE
Страница 1: ...r e b m u N e g a P d r a o b p il C Installation s Manual ...
Страница 2: ......
Страница 5: ...5 Navigation Trees 61 Blueface Thermostat Navigation Tree 61 Think Thermostat Navigation Tree 62 ...
Страница 34: ...34 Think Important In Think thermostats use to confirm and to return to the previous screen or menu ...
Страница 61: ...61 NAVIGATION TREES BLUEFACE THERMOSTAT NAVIGATION TREE ...
Страница 62: ...62 THINK THERMOSTAT NAVIGATION TREE Remember Use to confirm and for going back if browsing submenus ...