53
Error 10: Communication error between the BACnet Integration Gateway and the system
The system loses communication with the Airzone BACnet interface. Check that the gateway is properly connected to the
automation bus of the Control board.
Fig. 69
Error 11: Communication error between communication gateway and AC Unit
The system loses communication with the gateway and, therefore, with the AC unit. The system will open all the zones and
deactivate the control from the thermostats, only allowing the operation of the unit from the thermostat of its manufacturer.
To solve this incident check:
1.
Verify if the Air unit is powered. To do this, check the thermostat of the AC unit is ON.
2.
Verify the AC unit operates properly by itself. To do this, disconnect the A/C unit Airzone system and select the unit
from the thermostat from the A/C unit.
3.
Connection: Check the polarity and connection of the gateway connectors and the indoor unit. Consult the technical
sheet of the gateway in question.
4.
Wiring: In DIN-rail gateways, check that the voltage between the poles (A/ -) and (B/ -) is correct (0.65 Vdc).
5.
Verify the status of the LEDs of the gateway is correct. To do this check the self-diagnose section or the technical sheet
of the gateway.
Fig. 70
Error 12: Communication error between Airzone Cloud Webserver and the system
The system loses communication with the Webserver. Check that the Webserver is correctly connected to the Control board
automation bus.
Содержание AZVAF10KPROBE
Страница 1: ...r e b m u N e g a P d r a o b p il C Installation s Manual ...
Страница 2: ......
Страница 5: ...5 Navigation Trees 61 Blueface Thermostat Navigation Tree 61 Think Thermostat Navigation Tree 62 ...
Страница 34: ...34 Think Important In Think thermostats use to confirm and to return to the previous screen or menu ...
Страница 61: ...61 NAVIGATION TREES BLUEFACE THERMOSTAT NAVIGATION TREE ...
Страница 62: ...62 THINK THERMOSTAT NAVIGATION TREE Remember Use to confirm and for going back if browsing submenus ...