AZVAFZMxxxC
Fig. 74
Status LED
blinking purple quickly: Wireless Lite Thermostat- Zone Module communication error
(AZVAFDAMPERxxR / AZVAFZMRADR / AZVAFZMxxxR)
This incident blocks the control of the zone. To solve this incident check:
1.
Thermostat status: Check the signal range of the thermostat with the module through the Information parameter from
remote zones or approach the thermostat to the module if the thermostat recovers the communication, it is necessary
to relocate it as it was out of range.
2.
Module status: Correctly powered.
3.
Module status: Proper operation of the LED of wireless communication.
4.
Restart the zone and re-associate it with the system.
Remember: To reset to factory values of any Lite thermostat, turn up the microswitch 8 and place the thermostat on
the base again. Press on
, the LED will flash green twice when the reset process is completed.
5.
Restart system: If the system is restarted, this error may be displayed in the thermostats at the beginning of the process.
This message should disappear after around 30 seconds.
AZVAFDAMPERxxR / AZVAFZMRADR