Suburban DynaPack S & H Series Owner's Manual 06/2020 Rev.2 

2

 

WARNING

Installation and servicing of air conditioning equipment can be hazardous due to internal refrigerant pressure 

and  live  electrical  components.  Only  trained  and  qualified  service  personnel  should  install  or  service  this 

equipment. Installation and service performed by unqualified persons can result in property damage, personal 

injury, or death.

 

WARNING

For SAFE operation this must be installed using only the approved exterior grille and wall sleeve accessories. 

Failure to comply with this may result in property damage, personal injury, or death.

 

CAUTION

The installation of this appliance must conform to the requirements of the National Fire Protection Association; 

the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; the Canadian Electrical 

Code part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws or local ordinances. Local 

authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or 

requirements take precedence over the general instructions in this manual.

Chapter 1: Description and Specifications

  1.1 DESCRIPTION 

The DynaPack by Suburban Applied Products is a fully self-contained heating and cooling system that provides designers and builders 

with a cost effective alternative to condition multiple rooms in a multi-unit housing application.
The DynaPack features:

• 

1 to 2.5 Tons Cooling

• 

36 – 60 Input MBTU GAS Heat

• 

No Outside Condensing Unit

• 

S Series – Standard – 80% TE

• 

H Series – High Efficiency – 90%+ TE 

• 

R-410A Refrigerant

• 

Insulated 16 GA Coated Steel Base Pan

Do not operate the unit during construction period; this may be a breach of the warranty conditions.

  1.2  UNIT SPECIFICATIONS 

"S" Series

HEATING

COOLING

MODEL

12AC3A036 18AC3A036 24AC3A048 30AC3A060

MODEL

12AC3A036 18AC3A036 24AC3A048 30AC3A060

BTU INPUT

36,000

36,000

48,000

60,000

COOLING CAPACITY

12,000

18,000

24,000

29,500

VOLTS

208-230

208-230

208-230

208-230

VOLTS

208-230

208-230

208-230

208-230

AMPS

5.2

5.2

5.2

5.2

WATTS

1090

1636

2181

2681

GAS CONNECTION

1

/

2

 Inch Pipe at Unit

MCA*

12.9

19.0

20.5

23.4

*MCA= Minimum Circuit Ampacity

REFRIGERANT CHARGE

SEE INFORMATION STICKER ON UNIT

REFRIGERANT

R410A

"H" Series

HEATING

COOLING

MODEL

12AC3A039H 18AC3A039H 24AC3A052H 30AC3A052H

MODEL

12AC3A039H 18AC3A039H 24AC3A052H 30AC3A052H

BTU INPUT

39,000

39,000

52,000

52,000

COOLING CAPACITY

12,000

18,000

24,000

29,500

VOLTS

208-230

208-230

208-230

208-230

VOLTS

208-230

208-230

208-230

208-230

AMPS

4.7

4.7

4.7

4.7

WATTS

1090

1636

2181

2681

GAS CONNECTION

1

/

2

 Inch Pipe at Unit

MCA*

12.9

19.0

20.5

23.4

*MCA= Minimum Circuit Ampacity

REFRIGERANT CHARGE

SEE INFORMATION STICKER ON UNIT

REFRIGERANT

R410A

Содержание Suburban DynaPack H Series

Страница 1: ...m WARNING If the information in these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other...

Страница 2: ...and cooling system that provides designers and builders with a cost effective alternative to condition multiple rooms in a multi unit housing application The DynaPack features 1 to 2 5 Tons Cooling 36...

Страница 3: ...R CC BK BK BK 24 VAC GROUND Y W C R G PK HUM FLAME 24V FLAME SWITCH BL O 230V INDUCER BK R OFM C BK BR WHT GAS VALVE SWITCH HIGH LIMIT ROLLOUT SWITCH SWITCH PRESSURE O BL PK PK R O G BL Y BL BL BL O N...

Страница 4: ...units are vertical package units featuring gas fired heating with electrical air conditioning The Dynapack unit has been safety certified by Intertek Testing Services to comply with the national safet...

Страница 5: ...in any manner other than what is specified in these instructions The installation must be planned before hand so that the unit exhaust vent location complies with local or national codes in regards t...

Страница 6: ...of the units on each of the indoor blower speeds Table 4 lists the recommended heating and cooling speeds with its approximate cfm delivery Use both tables to properly design the duct system for both...

Страница 7: ...es to comply with the national safety codes of the USA and Canada The Dynapack unit is certified to operate on natural gas The Dynapack unit is NOT certified for installation in a mobile home Installa...

Страница 8: ...ed certain distances from adjacent doors operable windows and shrubbery See figure 11 at the end of this chapter CAUTION The unit must be installed level front to back and side to side Adjust front le...

Страница 9: ...1738 10 11 7 8 35 14 1744 1739 12 13 7 8 37 16 1745 1740 14 15 7 8 39 18 1769 1770 16 17 7 8 41 20 1771 1772 17 18 7 8 42 21 1773 1774 18 19 7 8 43 22 20 21 7 8 45 24 22 23 7 8 47 26 Table 4 E INSTALL...

Страница 10: ...he building drain system Use pvc pipe and fittings field supplied The wall sleeve is equipped with a drain pan that collects rain water entering the wall sleeve and the unit condenser coil area At the...

Страница 11: ...ing system during testing Once the gas piping up to the shut off valve has been tested the remaining piping to the unit gas valve must be tested Do not exceed psig or 14 water column for this test or...

Страница 12: ...ase the phase wire should be connected to L1 on the contactor An additional wire for unit grounding is required On 208 volt systems the transformer wiring needs to be changed Swap the red transformer...

Страница 13: ...TO WINDOW OR DOOR THAT MAY BE OPENED 6 INCHES 15cm FOR APPLIANCES 10 000 Btuh 3kw 12 INCHES 30cm FOR APPLIANCES 10 000 Btuh 3kw AND 100 000 btuh 30kw CANADIAN INSTALLATIONS US INSTALLATIONS 1 2 6 INC...

Страница 14: ...back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completion of installation the owner shall have a perio...

Страница 15: ...to run and the compressor will start Note There will be a 5 minute delay in the compressor starting if the thermostat set point was raised and then lowered again 12 Once the room reaches the set temp...

Страница 16: ...r conditioning performance If it is suspected that there is a refrigerant leak in the unit then the charge can be checked by placing a thermometer on the liquid line near the filter dryer and connecti...

Страница 17: ...er obstructions Clean the condensate drain and ensure there are no obstructions On DYPA12 models place a thermometer on the compressor suction line above the accumulator Connect a pressure gauge to th...

Страница 18: ...14 3 4 32 5 8 28 9 16 32 3 4 DYPA30AC3A 1741 5 7 8 6 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A and DYPA24AC3A 1742 7 7 8 8 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A and DYPA24AC3A 1743 9...

Страница 19: ...ted service labor diagnosis calls filter driers refrigerant or any other material charges 2 Damages caused by shipping accident abuse negligence misuse fire flood or Acts of God 3 Damages caused by op...

Страница 20: ...existing wires up to Top Line side of contactor 7 Wire as per drawing ES48000 sent with the kit to contactor ground lug 8 Re insert rubber drain hose through bushing with supplied Wires Heat cable 9 I...

Страница 21: ...ent un incendie ou une explosion pourrait en r sulter entra nant des dommages mat riels des blessures corporelles ou m me la mort Ne pas entreposer ni utiliser d essence ou d autres vapeurs ou liquide...

Страница 22: ...concepteurs et aux constructeurs une alternative conomique pour climatiser plusieurs pi ces dans un complexe d habitation Le DynaPack comporte 1 0 2 5 tonnes de refroidissement 36 60 MBTU de chauffag...

Страница 23: ...BK BK 24 V Ca TERRE Y W C R G PK HUM FLAMME 24V INTERRUPTEUR DE FLAMME BL O 230V INDUCTEUR BK R OFM C BK BR WHT ROBINET GAZ INTERRUPTEUR FIN DE COURSE INTERRUPTEUR ROTATIF PRESSOSTAT O BL PK PK R O G...

Страница 24: ...ynapack est une unit verticale comprenant un chauffage au gaz avec climatisation lectrique La s curit du Dynapack a t certifi e par Intertek Testing Services conform ment aux codes de s curit nationau...

Страница 25: ...d une mani re quelconque autre que celle qui est sp cifi e dans ces instructions L installation doit tre planifi e l avance afin que l emplacement de l vent de l appareil soit conforme aux codes loca...

Страница 26: ...e Approx CFM Approx Hausse Temp F Vitesse de refroidissement recommand e Approx CFM DYPA12AC3A036 moyenne 700 38 Bas 400 DYPA12AC3A048 moyenne 700 50 Bas 400 DYPA18AC3A036 moyenne 700 38 moyenne basse...

Страница 27: ...t aux codes de s curit nationaux des tats Unis et du Canada Le Dynapack est certifi pour fonctionner au gaz naturel Le Dynapack n est PAS certifi pour installation dans une maison mobile Les installat...

Страница 28: ...des buissons Voir la figure 11 la fin de ce chapitre MISE EN GARDE L appareil doit tre install niveau de l avant l arri re et de c t c t Ajustez les pieds de nivellement avant selon besoin B INSTALLAT...

Страница 29: ...7 8 31 10 1742 1737 8 9 7 8 33 12 1743 1738 10 11 7 8 35 14 1744 1739 12 13 7 8 37 16 1745 1740 14 15 7 8 39 18 1769 1770 16 17 7 8 41 20 1771 1772 17 18 7 8 42 21 1773 1774 18 19 7 8 43 22 20 21 7 8...

Страница 30: ...syst me de drainage du b timent Utilisez des tuyaux de et des raccords en PVC fournis par l installateur Le caisson mural est quip d un bac de r cup ration des eaux de pluie qui p n trent dans le cai...

Страница 31: ...ssion d essai de la tuyauterie de gaz Sinon de la vanne de fermeture doit tre retir e du syst me de tuyauterie pendant les tests Une fois que la tuyauterie de gaz a t test e jusqu la vanne de fermetur...

Страница 32: ...e est de 208 230 volts phase neutre Dans ce cas le fil de phase doit tre connect L1 sur le contacteur Un fil suppl mentaire pour la mise la terre de l appareil est requis Sur les syst mes 208 volts le...

Страница 33: ...LES APPAREILS 50 000 Btuh 15 kW 6 POUCES 15cm POUR LES APPAREILS 10 000 Btuh 3 kW 9 POUCES 23 cm POUR LES APPAREILS 10 000 Btuh 3 kW ET 50 000 Btuh 15 kW 12 POUCES 30 cm POUR LES APPAREILS 50 000 Btuh...

Страница 34: ...u prochain tage adjacent b Si les exigences de la pr sente sous section ne peuvent tre satisfaites au moment de l installation le propri taire dispose d un d lai de trente 30 jours pour se conformer a...

Страница 35: ...le compresseur se met en marche Remarque il y aura un d lai de 5 minutes au d marrage du compresseur si le point de consigne du thermostat a t lev puis nouveau abaiss 12 Une fois que la pi ce a attei...

Страница 36: ...ME L unit a t test e en usine pour assurer des performances appropri es de la climatisation Si l on soup onne une fuite de r frig rant dans l appareil la charge peut tre v rifi e en pla ant un thermom...

Страница 37: ...at et assurez vous qu il n y a pas d obstruction Sur les mod les DYPA12 placez un thermom tre sur la conduite d aspiration du compresseur au dessus de l accumulateur Connectez un manom tre au port de...

Страница 38: ...14 3 4 32 5 8 28 9 16 32 3 4 DYPA30AC3A 1741 5 7 8 6 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A et DYPA24AC3A 1742 7 7 8 8 3 4 28 5 8 28 9 16 28 3 4 DYPA12AC3A DYPA18AC3A et DYPA24AC3A 1743 9 7 8...

Страница 39: ...ande l ex cution au titre de cette Garantie doit fournir un acc s raisonnable au produit ou la pi ce pr tendument d fectueux ou d faillant Airxcel Commercial Group et ses agents et employ s autoris s...

Страница 40: ...t sup rieur ligne du contacteur 7 C blez selon le plan ES48000 envoy avec le kit au contacteur et la cosse de terre 8 R ins rez le tuyau de drainage en caoutchouc dans la bague avec les fils c ble de...

Отзывы: