background image

Purging the Heating Loop

Purging the Heating Loop

©Aqua-Hot®

 125DN Installation Manual 

REV 220419

©Aqua-Hot®

 125DN Installation Manual 

REV 220419

p. 47

p. 46

Fuel Purge Procedure:

The  fuel  lines  should  be  automatically  primed  with  the  first 

operation of the burner. It may need to be power cycled a few 

times (3-4 times) to purge any air. Perform this procedure once 

the burner and Aqua-Hot are completely installed and the Aqua-

Hot is adequately filled and purged.

1.  Connect a 6V power source to the fuel pump to pulse 

the pump. The power source must be able to be pulsed 

(turned on and off) rapidly, for this process.

•  The pump can be powered with wire and gator 

clips.

•  The pump pin numbers can be found on the inside 

of the housing where the pins are found.

•  Ground goes to Pin #1

•  Power goes to Pin #2

•  If you would rather use a plug instead of the wire 

and gator clips, the mating part numbers needed 

for the connector are:

○  Housing: 1-967644-1

○  Terminal; 0965906-1

○  Seal: 0-967067-1

2.  Pulse the fuel pump at a steady 1-2 pulses per second 

until fuel begins to come out of the fuel line where it 

will connect to the burner.

3.  Connect the fuel line to the burner.
4. 

Ensure all hose clamps and fuel fittings are tight and 

properly secured.

5.  Ensure that the exhaust is well ventilated.
6.  Turn the burner to ON at the screen (see Figure 98). 

The burner should cycle on because of the primed fuel  

lines.

•  There may be smoke from the exhaust on initial 

start-up, this is  normal.

7. 

If the burner does not cycle on with the first start up, it 

will try a second time.

•  If the second start-up fails, there will be a fault 

message on the LCD screen (Figure 99). Tap the 

burner OFF at the screen.

•  Repeat Step 6.
•  If fault occurs again, repeat Steps 4-6.

8.  After a successful start up, run the burner for 5 

minutes.

9.  After running the burner for 5 minutes, tap the HIGH 

ALTITUDE option on the LCD screen (see Figure 100) 

and run for additional 2 minutes.

After a complete, successful first operation, the fuel lines should 

be purged of any air and ready for normal operation and use.

Fuel System Purge

Figure 98

Figure 99

Figure 100

Fuel Pump Pins

Figure 97

1      2

Do NOT exceed 6V when powering the fuel pump. This can 

cause irreparable damage to the fuel pump.

NOTE:

 DO

 NOT

 run the diesel burner without the coolant filled 

and purged as it will cause serious damage to the burner.

External Diesel Burner Troubleshooting

This section will cover any issues with the external diesel burner. The diesel burner is the primary heat source to the 125GN.  
The troubleshooting procedures listed below are arranged in order of repair complexity. Do not replace parts without correctly 

determining the failure.

Follow the directions below in order to troubleshoot the diesel burner. Do not skip through the troubleshooting steps, as this 

may needlessly complicate unit diagnosis and repair.

Troubleshooting Procedure:

•  Ensure that the system is supplied with electrical power and there are no blown fuses.
• 

Ensure that there is at least ¼ tank of fuel in the vehicle fuel supply and the fuel filter is not clogged.

•  Make sure all the electrical and plumbing connections are connected and secure.
•  Ensure there are no faults for the burner. If there are, determine the fault and remedy.

The fault is indicated by a flashing “fault” light on the LCD screen during heater operation. It is indicated on the diagnostic screen 

by the Burner Status ON/OFF indicator. There will be a series of rapid flashed, followed by 1 or more slow flashes. The rapid flashes 

are an alert indicator; the slow flashes should be counted, as that is the fault code. Refer to the table below for the fault code.

FO1 (1 flash)

No start (after 2 attempts to start

FO2 (2 flashes)

Flame failure

F03 (3 flashes)

Under-voltage or over-voltage

F04 (4 flashes)

Premature flame recognition 

F05 (5 flashes)

Not used

F06 (6 flashes)

Coolant temperature sensor interrupt or 

temperature sensor short-circuit

F07 (7 flashes)

Fuel pump interrupt or short-circuited

F08 (8 flashes)

Combustion air fan motor interrupt or blower 

motor short-circuit or incorrect speed

F09 (9 flashes)

Flame sensor interrupt or short-circuit

F10 (10 flashes)

Overheating

F11 (11 flashes)

Circulating pump interrupt or short-circuit 

F12 (12 flashes)

Battery main switch short-circuit

F13 (13 flashes)

Output vehicle fan short-circuit

F14 (14 flashes)

Overheating sensor defective

F15 (15 flashes)

Pre-heating/ignition circuit defective

F16 (16 flashes)

Exhaust gas temperature too high

F17 (17 flashes)

Exhaust gas temperature sensor defective

After 5 short signals, count the long flashes:

F00 (continuous 

flashing)

Burner interlock (lock-out

After the fault cause has been eliminated, the burner must be 

switched on again.

Heater Lock-out Reset Procedure

The control unit continuously monitors the heater operation. 

The control unit identifies errors on individual burner com

-

ponents and faults during operation. Should the control unit 

experience component errors and operational faults, the 

burner may be shut down and not restart.
The burner lockout reset must be done manually as shown 

below.

Troubleshooting Procedure:

•  Turn on the burner on the interior switch.
•  Remove the main power connection to the burner or pull 

the fuse for a minimum of 20 seconds.

•  Turn the burner off on the switch.
•  Reconnect the main power connection that was previously 

disconnected.

External Diesel 

Burner

Figure 101

Burner Troubleshooting

Содержание AHE-125-DN1

Страница 1: ...Installation Manual 100Series AHE 125 DN1...

Страница 2: ...urging the Interior Heating Loop 41 Fuel Supply 42 Fuel System 43 Fuel Purge Procedure 46 External Diesel Burner Troubleshooting 47 System Checks 49 First Operation 50 Winterizing 51 Flow Diagram 52 A...

Страница 3: ...Aqua Hot 20 Aqua Hot to Heat Source port connected to Burner In Port 21 23 Aqua Hot from Heat Source port connected to Burner Out Port 21 23 RV Thermostats OR Thermistors wired to Aqua Hot 24 25 House...

Страница 4: ...ll shut down all fans heat sources and pumps until the unit is adequately refilled House Power Sense The Aqua Hot Controller contains within it a fail safe functionality known as House Power Sense Thi...

Страница 5: ...our on product identity label contains the specifications of your unit Factory settings may be adjusted by the vehicle manufacturer confirm final setting with your dealer This heating system has been...

Страница 6: ...2 NOTE This product label shown above is attached to the side of the burner and provides a ready reference to specifications test standards and important safety notices 1 Fluid Circulation Pump 2 Tem...

Страница 7: ...Aqua Hot in place on the RV floor Use at least 1 screw per mounting tab 3 tabs The best place for the Aqua Hot heating system is in a cabinet or storage space making sure there is ample space to remov...

Страница 8: ...OTE Avoid any bends or dips in the overflow tubing from the Aqua Hot Air can become trapped in these bends and will prevent excess antifreeze and water heating solution from depositing properly in the...

Страница 9: ...recommended to use a minimum of three mounting holes Do NOT mount the fuel pump higher than the fuel inlet on the burner see Figure 7 on Page 8 and the Fuel System section pages 40 44 for reference Hi...

Страница 10: ...the interior of the vehicle only the exterior Failure to do so can cause exhaust gas to leak inside the vehicle causing illness and or death The specifications and requirements must be followed carefu...

Страница 11: ...3041 Terminal TE Connectivity 828905 1 Wire Seal X6 Connector Figure 33 Figure 36 Figure 35 Diesel Burner Wire Harness The diesel burner and connectors will need to be properly installed Please note t...

Страница 12: ...ircuits Connecting the Burner to the Aqua Hot These instructions will cover the installation and connections for the diesel burner to the 125DN Installation Instructions 1 Mock up the locations for th...

Страница 13: ...ot re cut the thread multiple times The screw must be carefully inserted in the existing threads and screwed in by hand Burner Connections Retaining Plate 15mm Self Tapping Screw Plumbing Requirements...

Страница 14: ...ntacts Once the required hardware has been acquired wire the J8 plug according to the table below Pins J8 10 through J8 15 are not utilized Pin Number Function Connect To J8 1 Zone 1 Thermostat In Zon...

Страница 15: ...Special If for some reason pin J3 1 cannot be supplied with power supply 12V DC power to the J8 9 pin 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 J8 Wire Insertion View Shown J3 Wire Insertion View Shown Fig...

Страница 16: ...to the vehicle s AC electric system Connect the 3 pin Molex connector to the coach side AC electric system in order to utilize the Aqua Hot s AC heating element The Aqua Hot utilizes Molex 19403 and 1...

Страница 17: ...ly to be contaminated Aqua Hot advises against placing a heat exchanger on the slide out section of any vehicle due to the high probability of damage occurring to the heating loop from moving parts Fi...

Страница 18: ...installation principles can hinder the operation of the heat exchangers All plumbing should be installed as flatly as possible Extreme rises in height should be avoided to avoid any potential air tra...

Страница 19: ...nk is up at operating temperature Activate the external diesel burner to provide adequate heat for hot water needs The electric element will only provide light duty hot water The tempering valve is in...

Страница 20: ...e of zone thermostats used within the RV Section 1A demonstrates the appearance of the zone control section when ON OFF thermostats are used within the RV In this use case these buttons serve only as...

Страница 21: ...his option toggles the Aqua Hot s quiet mode Quiet mode is a setting where the speed and output of the heat exchanger fans is reduced to 80 This is done to reduce noise of the heat exchangers Please n...

Страница 22: ...ternal pump in the receptacle which contains the heating solution Make sure to select the correct glycol antifreeze product for the external heating source Failure to select the correct product could...

Страница 23: ...e fuel tank Vehicle Fuel Tank Figure 90 Fuel Supply Failure to follow instructions on the fuel delivery system can cause damage to the Aqua Hot 125DN the diesel burner or the RV It may cause serious p...

Страница 24: ...Clamp B Bubble B A A B NOTE The fuel lines must be secured and supported properly to avoid air traps or bubbles Avoid unnecessary dips or bends the line should not run downward from the fuel pump High...

Страница 25: ...omplexity Do not replace parts without correctly determining the failure Follow the directions below in order to troubleshoot the diesel burner Do not skip through the troubleshooting steps as this ma...

Страница 26: ...here should be substantial separation from the burner and the ground 7 There should be enough space between the vehicle body and any heat generating components like the exhaust and burner 8 Ensure the...

Страница 27: ...o perform the fuel line purge procedure on Page 44 prior to starting this initial start up of the burner Winterizing the Aqua Hot Not winterizing the Aqua Hot when freezing temperatures are present wi...

Страница 28: ...r and Diesel Burner DIESEL BURNER AUTO AIR BLEED AUTO AIR BLEED 3 WAY VALVE COOLANT TEE RECOVERY BOTTLE FILL PORT BALL VALVE 3 Way Valve Controls Coolant Flow Path For Interior or Hot Water Heating In...

Страница 29: ...eating Loop Purging the Heating Loop Aqua Hot 125DN Installation Manual REV 220419 Aqua Hot 125DN Installation Manual REV 220419 p 55 p 54 System Schematics ZONE THERMOSTATS System Schematics ZONE HEA...

Страница 30: ...ating Loop Purging the Heating Loop Aqua Hot 125DN Installation Manual REV 220419 Aqua Hot 125DN Installation Manual REV 220419 p 57 p 56 System Schematics EXTERNAL DIESEL BURNER System Schematics ELE...

Страница 31: ...he next step Adjust the Boundary Line Once the glycol solution has been properly applied adjust the calibration screw until the boundary line labeled Ethylene Glycol is set to 32 F The graphic to the...

Страница 32: ...Room Temperature Sensor Parts Accessories EXX 950 411 Grille 10 x 2 Cozy EXX 006 500 Grille Long 3 5 x 21 5 Black EXE 505 65A Heat Exchanger Whisper Silent 12V DC EXX 013 100 Nozzle Round 4 w o Connec...

Страница 33: ...FL1 Kit Fuel Line 125DN PLX 000 200 Tube Safety Stripe 12ft PLX 000 820 Fitting Elbow 90 Barb Black Nylon PLX 000 835 Fitting Reducer to Black Nylon Parts Accessories PLX 200 103 Fitting M NPT x Barb...

Страница 34: ...e use of accessory parts or parts not authorized by Aqua Hot Heating Systems Inc repair by unauthorized persons and damage or abuse of the heater are specially excluded from warranty coverage For addi...

Страница 35: ...ting Systems LLC 7501 Miller Drive Frederick CO 80504 Visit us online at www aquahot com Call us at 800 685 4298 or 303 651 5500 2022 Aqua Hot Heating Systems LLC Printed in the USA Installation Manua...

Отзывы: