4.16
P1 Troubleshooting
Digital display output
4.16.1
Description
4.16.2
Discharge pipe high pressure protection. When the discharge pressure rises above 4.2MPa, the system displays
P1
protection and
Wellea
Mono stops running. When the discharge pressure falls below 3.2MPa, P1 is removed and
normal operation resumes.
Error code is displayed on refrigerant system main PCB and user interface.
Possible causes
4.16.3
Pressure sensor/switch not connected properly or has malfunctioned.
Excess refrigerant.
System contains air or nitrogen.
High pressure side blockage.
Poor condenser heat exchange.
Main PCB damaged.