Wellea Monobloc
67
Procedure
4.13.4
H7
Power supply voltage is not within ±10%
of rated voltage or a (on 3-phase models)
phase is missing
Yes
Provide normal power supply
No
Wires between refrigerant system main
PCB, AC filter board (on 3-phase models)
and electric control box power supply
terminals are loose
Yes
Ensure the wires are connected properly
No
Outdoor unit powered on immediately
after being powered off
Yes
Power-off the unit and wait for at least 3
minutes before powering-on
No
High voltage circuit error has occurred,
such as the compressor has
malfunctioned, the fan motor has
short-circuited, or the inverter module
has short-circuited
Yes
Replace or repair the relevant parts
No
Replace refrigerant system main PCB