H6, HH Troubleshooting
4.12.1
Digital display output
Description
4.12.2
H6 indicates a DC fan error.
HH indicates that H6 protection has occurred 10 times in 2 hours. When an HH error occurs, a manual system
restart
is required before the system can resume operation. The cause of an HH error should be addressed
promptly in order
to avoid system damage.
Wellea
Mono stops running.
Error code is displayed on refrigerant system main PCB and user interface.
Possible causes
4.12.3
Power or communication wires not connected properly.
High wind speed.
Fan motor blocked or has failed.
Power supply abnormal.
PFC module damaged.
IPM module damaged.
Main PCB damaged.