24
Wellea Monobloc
Table 3-7.3: Component control during defrosting
operation
Component
Wiring diagram
label
5/7/9kW
12/14/16
kW
Control functions and states
Inverter compressor
COMP
●
●
Runs at defrosting operation rotation speed
DC fan motor / Upper DC fan motor
FAN1 / FAN_UP
●
●
Off
Lower DC fan motor
FAN_DOWN
●
Electronic expansion valve
EXV
●
●
Fully open
Four-way valve
ST
●
●
Off
6.3
Fast DHW Operation
Fast DHW operation is used to quickly meet a requirement for domestic hot water when DHW priority has been set on
the user interface. Refer to the
Wellea
Mono Engineering Data Book Part 3, 7.4 “DHW MODE SETTING Menu”.
Domestic hot water demand priority can be ended by changing the switch on controller from "on" to "off".
Table 3-7.5: Component control during fast DHW operation
Component
Wiring diagram
label
5/7/9kW
12/14/16kW
Control functions and states
Inverter compressor
COMP
●
●
Controlled according to load requirement
DC fan motor / Upper DC fan motor
FAN1 / FAN_UP
●
●
Controlled according to outdoor heat exchanger
pipe temperature
Lower DC fan motor
FAN_DOWN
●
Electronic expansion valve
EXV
●
●
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge superheat
Four-way valve
ST
●
●
On
Tank electric heater
TBH
●
●
On