2-12
PRODUCT DATA SHEET
SM YAZDCI 1-A.1 GB
2.3.19
HAD009 DCI Specifications
Model Indoor Unit
HAD009 DCI
Installation Method of Pipe
Flared
Power supply
V/Ph/Hz
220-240/1/50
INDOOR
Fan type & quantity
Crossflow x 1
Fan speeds
H/M/L
RPM
1150/1000/800
Air flow
(1)
H/M/L
m3/hr
420/350/270
External static pressure
Min
Pa
0
Sound power level
(2)
H/M/L
dB(A)
54
Sound pressure level
(3)
H/M/L
dB(A)
40/35/29
Moisture removal
l/hr
1.0
Condenstate drain tube I.D
mm
16
Dimensions
WxHxD
mm
680 x250 X188
Net Weight
kg
7
Package dimensions
WxHxD
mm
740x310x248
Packaged weight
kg
10
Units per pallet
units
32
Stacking height
units
8
2.3.20
HAD012 DCI Specifications
Model Indoor Unit
HAD012 DCI
Installation Method of Pipe
Flared
Power supply
V/Ph/Hz
220-240/1/50
INDOOR
Fan type & quantity
Crossflow x 1
Fan speeds
H/M/L
RPM
1150/950/750
Air flow
(1)
H/M/L
m3/hr
550/450/350
External static pressure
Min
Pa
0
Sound power level
(2)
H/M/L
dB(A)
56
Sound pressure level
(3)
H/M/L
dB(A)
40/34/28
Moisture removal
l/hr
1.5
Condenstate drain tube I.D
mm
16
Dimensions
WxHxD
mm
840x250x188
Net Weight
kg
8
Package dimensions
WxHxD
mm
900x310x248
Packaged weight
kg
11
Units per pallet
units
32
Stacking height
units
8
NOTE:
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511.
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1 meter distance from unit.