11-13
CONTROL SYSTEM
SM YAZDCI 1-A.1 GB
11.5.3 EEV
Control
11.5.3.1 Operation
Range
The EEV operation range is defined according to the operation mode as following
ODU Mode
Normal operation
IDU inactive
Compressor off
SB
400
400
COOL
50
to
480
0
HEAT
50
to
480
50
to
120
11.5.3.2
Reaching target value rules
For all cases except at EEV initialization procedure, each EEV can move no more than
20
steps
at a time.
When required the EEV’s move, one by one in sequence, till the target position is achieved for
every EEV.
The following diagram presents the EEV steps till the target position is set.
EEV1
EEV2
EEV3
EEV4
EEV1
EEV3
EEV4
EEV3
EEV4
EEV3
EEV3
EEV2
set
EEV1
set
EEV4
set
EEV3
set
11.5.3.3 EEV
homing
When compressor stops or unit is power on, the following is performed immediately:
All EEV’s are set to
-
400.
They remain in this position for
-
80
Sec.
Then, close to 60 steps below 0 to ensure full closure, then proceed to normal operation
-
11.5.3.4
EEV Opening Determination
The target EEV value is the sum of open loop value (OL) and a result of the accumulative
correction values (CV).
CVi
OLi
i
EEV
EEV
EEV
EEVi
is the EEV opening for each ‘i’ IDU.
11.5.3.5
EEV initial value determination
The EEV initial value (open loop) is determined according to the number of the active indoor
units, mode, and the capacity code of the unit.
EEVBase
Base open loop
(Nominal Conditions/Capacity Code=1/MaxFrequency)
EEVCpctyCrct
Capacity code correction
Unit Type
ODU
Mode
Number of active IDU units
IDU Capacity Group
1
2
3
4
0
1
3
4
Multi
(Active IDU)
COOL
250
210
170
150
0
25
80
110
HEAT
230
190
150
130
0
25
90
110
Multi
(In Active IDU)
Cool
NA
NA
Heat
90
0