34
User Menu / ADVANCED CONFIGURATION
Lock Device
Lock the unit with code. The unit will be OFF
while locked.
Parameters
Configure Advanced parameters
IN/OUT
Configure the functions at:
•
Digital IN
•
Digital OUT
•
Analog IN
•
Analog OUT
Configure temperature sensors
Configure connections
Change Advanced Code
You can modify the password
Recovery to default
It turns all parameters to default except the
selection made in initial configuration
User Menu / Advanced Configuration / ADVANCED PARAMETERS
Intervals
Intervals are used at automatic programs to
modify the ventilation and heating in order to
have the most efficient separation.
Set/Ambient Temp: 2ºC default
Set/External Temp: 2ºC default
Hysteresis: 1ºC default
Fans Overheating
Determines the time the fan stops if there is
a fan overheating.
If it happens more than “X” times in “Y”
interval, the heating will be blocked.
Time of initial stop: 120seg by default
Detection number: 2 times by default
Time interval: 30 min by default
Fan RPM
Under construction
Int Modulation P5 0-10V sec
At program 5, establishes the interval of
modulation in seconds.