Modbus RTU: 

 

Modbus system only allows 1 manager. So we should only send orders to the unit by BMS or TFT Clever (if both 

together there will be problems). 

 

To avoid communication troubles, you should use two different ports: TFT trough Modbus RTU1 and BMS at Modbus 

RTU2. See following diagram: 

 

 

Using the TFT you can select different baud rate at each port (by default is 115.200). Before starting, be sure that port 

RTU2 has the same speed as BMS. 

 

If you want to send orders via Modbus you should: 

1.

 

Lock the TFT to avoid that nobody is sending also orders to the Clever (only 1 manager). You can lock using the 

same code of TFT or another different (then people won’t be able to unlock from TFT as they won’t know the 

code). 

2.

 

Stop the timer to avoid undesired ON Day/Night or OFF 

3.

 

Manage the unit: 

 

ON/OFF unit 

 

Select Energy Saving Mode (Comfort/Medium/Eco) 

 

Select the functioning mode: 

 

If MANUAL, you can select: 

 

Fan speed 

 

Heating stages 

 

Temperature SET 

 

If AUTOMATIC, you only can change the temperature SET 

 

If you want to stop managing the equipment from BMS and activate the Clever TFT to allow the people manage the unit, 

then you only have to unlock the TFT (and stop giving Modbus orders).  

If you have locked the controller using a different code than TFT, you have to unlock with the old TFT code (Known by 

people that uses TFT). 

Содержание CLEVER CONTROL V3

Страница 1: ...UAL USER AND BASIC VERSION Please read these instructions carefully before attempting installation SECURITY ADVISE SIMBOLS Attention Danger Safety Advice Danger from electric current of high voltage I...

Страница 2: ...S 21 User Menu Basic Configuration WORKING PROGRAM FAN HEATERS 22 User Menu Basic Configuration CONFIGURATION INITIAL 23 User Menu Basic Configuration Configuration NAME 24 User Menu Basic Configurati...

Страница 3: ...ver Control has 3 grades of comfort and energy efficiency which can be adjusted in all manual and automatic programs Eco mode uses the less energy possible without compromising too much the comfort wh...

Страница 4: ...ation mode user can set the minimum maximum of many parameters like ventilation speed or heating when door is open closed set the temperatures for day night and air outlet the door delay etc Advanced...

Страница 5: ...tion INTELLIGENT PCB If more than one PCB connected in serial using Modbus protocol you should turn ON the 3 switches inside the Clever Control and use 3 jumpers at CN3 CN6 and CN7 according to the wi...

Страница 6: ...6 CONNECTION DIAGRAM TEMPERATURE SENSOR SHIELDED CABLE CONNECTION DIAGRAM AIR CURTAIN 1 Clever Control managing 1 unit 1 PCB...

Страница 7: ...RAM AIR CURTAIN 1 Clever Control managing multiple units 1 PCB Please consult the operating manual of the air curtain for multiple units connection Connection Diagram FAN HEATER 1 Clever Control manag...

Страница 8: ...N HEATER 1 Clever Control managing multiple units 1 PCB Connection Diagram HORIZONTAL FAN HEATER 1 Clever Control managing multiple units 1 PCB Please consult the instruction manual of the fan heater...

Страница 9: ...9 Wiring Diagram 1 Clever Control with 1 Intelligent PCB...

Страница 10: ...10 Wiring Diagram 1 Clever Control with 2 Intelligent PCB...

Страница 11: ...00000001 10000000 2 00000010 01000000 3 00000011 11000000 4 00000100 00100000 5 00000101 10100000 6 00000110 01100000 7 00000111 11100000 8 00001000 00010000 9 00001001 10010000 10 00001010 01010000 3...

Страница 12: ...R TFT CONTROL MAIN STATE SCREEN Main state screen indicates of the most important settings including Ventilation speed heating temperatures door state working mode and program filter state day hour ti...

Страница 13: ...evice externally or by the BMS UNIT LOCKED Indicates that the unit is locked Unit does not work until you unlock it by code CONTROL LOCKED Indicates that the control is locked Unit works but user need...

Страница 14: ...then arrows buttons will modify the heating If you press again then arrows modify the temperature set Auto Modifies only the Set temperature Menus Scroll through option left or editing value between a...

Страница 15: ...can edit an option USER MENU SCREEN 1 Select Operation Mode Automatic or Manual Functioning Select Energy Saving Mode Eco Uses the less energy possible Medium In between Eco Comfort modes Comfort Spe...

Страница 16: ...as Disable To activate to turn it into Enable and press button to activate it and show all the options TIME PROGRAMMER MENU SCREENS 1 y 2 Enable Disable Time Programmer Select Day Type group Create fr...

Страница 17: ...e programmed daily with desired schedule Mon Fri Monday to Friday Mon Sat Monday to Saturday Mon Sun Monday to Sunday Mon Fri Sat Monday to Friday and separately Saturday Mon Fri Sat Sun Monday to Fri...

Страница 18: ...n Confirm Should press to confirm your selection and go back to Timer general menu Delete If you want to delete the editing action select Yes and press User Menu ADJUST TIME This function adjusts the...

Страница 19: ...and go back to general User Menu User Menu BASIC CONFIGURATION MENU In Basic Configuration mode the technician can configure the main parameters of the clever control BASIC CONFIGURATION SCREEN MENU...

Страница 20: ...eating unheated electrical heated water heated heat pump Energy saving mode Eco Medium or Comfort Manual P1 Manually you can select ventilation speed and heating stage also with heat pump units you ca...

Страница 21: ...nergy saving mode P2 Functioning according to o Set and external temperature o Door state o Energy saving mode P3 4 Functioning according to o Door opened Set Temperature and External Temperature o Do...

Страница 22: ...omfort nothing is modified Medium heating is stopped Eco stops the air curtain Automatic Depending on program Clever will regulate itself the ventilation and heating thanks to its temperature sensors...

Страница 23: ...default Unit Modbus address Select the fan speed Air Curtains 2 or 5 Select the heating Air unheated Electrical heated Water heated or Heat Pump New questions options can appear if required CONFIGURA...

Страница 24: ...T Enter name less than 12 digits 1 Use Scroll Up Down buttons to move through all characters available Press button to select and move to next character 2 If the name is completed before reaching the...

Страница 25: ...s that will activate the General Alarm If only 1 of those alarms is activated the general alarm will be also activated GENERAL ALARM MENU SCREEN 1 Overheating Alarm Autocooling Alarm Dity Filter Alarm...

Страница 26: ...eating alarm It indicates that there is an overheating inside the fans of the unit Heating Lock Alarm It indicates that the heating has been blocked Air Flow alarm It indicates that the airflow is too...

Страница 27: ...p Down User Menu Basic Configuration Parameters SPEED buttons to move and select an option When option is highlighted in blue press button to enter and edit Min Max Speed when Door Open Min Max Speed...

Страница 28: ...he heat pump when door closes waiting the selected minutes If door is opened again before this time elapses heat pump will not be turned OFF User Menu Basic Configuration Parameters HEATING Min Voltag...

Страница 29: ...et User Menu Basic Configuration Parameters Temperature CALIBRATION Sensors Calibration These parameters allow to calibrate each temperature sensor with X C plus or minus degrees User Menu Basic Confi...

Страница 30: ...t nominal speed or heating when you open the door you can program at temporized door out signal how many seconds the door should remain closed while the air curtain is preparing itself Once this time...

Страница 31: ...tects how many times the door is open for the last minutes and adapts the door delay times and strengths to those conditions in order to save energy Fixed You can set how many seconds will stay at ste...

Страница 32: ...Menu Basic Configuration COUNTERS Filter Hours To Next Revision It displays the hours without changing the filter total hours before filter alarm 50 300 working 50h since last filter alarm and remain...

Страница 33: ...ly for professionals please consult If you want to protect the control from end users you can lock the control or the unit User protections Control Locked Code 1234 by default unit will remain working...

Страница 34: ...Advanced Configuration ADVANCED PARAMETERS Intervals Intervals are used at automatic programs to modify the ventilation and heating in order to have the most efficient separation Set Ambient Temp 2 C...

Страница 35: ...puts Modify the functions of Analog Outputs Temperature sensors Modify the functions of temperature sensors Communications Configure the communications You can select a function to each Digital IN Eac...

Страница 36: ...lt Sensor 1 Outdoor Sensor 2 Air Discharge Sensor 3 Inside Controller Enabled Yes Inside sensor has priority to the controller s one If it s not connected automatically uses the TFT control When you c...

Страница 37: ...37 Connections and Functions IN OUT of Digital Analogic and Temperature sensors...

Страница 38: ...38...

Страница 39: ...39 There is an ADVANCED MANUAL that explains deeply the functioning and configuration of all functions of Digital IN Digital OUT Analog IN Analog OUT...

Страница 40: ...inning of this manual you can see the default functions of each entrance There are more functions than entrances so you can select the most appropriate to cover your needs advanced menu All digital IN...

Страница 41: ...lever only 1 manager You can lock using the same code of TFT or another different then people won t be able to unlock from TFT as they won t know the code 2 Stop the timer to avoid undesired ON Day Ni...

Страница 42: ...2 At the following page there are all the needed Modbus orders to manage the units All changes will not be saved if the power supply stops To avoid it after any order you have to save the configuratio...

Страница 43: ...in 2 halves Identify wall connection In case of not having a wall switch box use Clever s wall support accessory Mount the back cover inside the wall switch Connect RJ11 Cable to Clever s PCB connect...

Отзывы: