11
MODIFY MODBUS ADDRESS
By default the Modbus address of Clever PCB is 1.
If more than one PCB is connected in serial using Modbus protocol, you should give different Modbus
addresses to each PCB board (you can choose from 1 to 255). The Modbus addresses should be introduced
using a binary code to the switch SW1 as examples shown in this table:
PCB number (decimal)
Binary code
PCB switch position
1
00000001
10000000
2
00000010
01000000
3
00000011
11000000
4
00000100
00100000
5
00000101
10100000
6
00000110
01100000
7
00000111
11100000
8
00001000
00010000
9
00001001
10010000
10
00001010
01010000
34
00100010
01000100
58
00111010
01011100
100
01100100
00100110
After choose an address, you should open the board and turn ON and OFF the correct switches of SW1 for the
desired Modbus address. For example:
After modify the new Modbus address, you should:
•
Remove the power supply or click the reset button 2 seconds
•
Go to initial configuration (basic menu) and press “SCAN” to update all Modbus addresses.