En-11
(3) Connect the cable of wired remote controller unit to the PCB of Control unit, and set
the DIP switch (SW1). Fasten the remote controller cable to the EV kit cable with the
cable tie as shown below.
CAUTION
When switching the DIP switch (SW1), be sure to turn off the power supply to the
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.
For 2-wire type
For 3-wire type
Set the DIP switch (SW1)
2WIRE (Factory setting)
3WIRE
DIP switch
(SW1)
SW1
3WIRE
2WIRE
Connector
(CNC01)
Connecting cable
(Accessories)
Wired remote
controller cable
Cable tie
(Accessories)
10 mm
or less
To EV kit
6.6. External input and external output
(Optional parts)
Controller PCB
Output terminal
(CNB01)
(CNA01)
(CNA02)
(CNA03)
(CNA04)
OFF
ON
DIP switch
(SET 2)
Dry contact
terminal
Apply voltage terminal
SW4
SW3
SW2
SW1
(1) External input
• Indoor unit can be Operation/Stop or Emergency stop or Forced stop by using indoor
unit PCB CNA01 or CNA02.
• “Start/Stop” mode or “Emergency stop” mode or “Forced stop” mode can be selected
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
●
Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
Input
de
vic
e 1
Input
de
vic
e 2
Input
de
vic
e 3
Load
resistance
Load
resistance
Load
resistance
*1
DC power supply
12 to 24V
connected unit
*a
*a
*a
P.C.B
CNA01
CNA03
*b
*1 Make the power supply DC12 to 24V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
When connected to Apply voltage terminals of multiple indoor units with a connected unit,
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
DC power supply
12 to 24V
connected unit
Load
resistance
P.C.B
P.C.B
CNA01
P.C.B
Input
de
vic
e 1
Input
de
vic
e 2
Indo
or
unit
Indo
or
unit
Indo
or
unit
Load
resistance
CNA01
CNA01
●
Dry contact terminal ([CNA02], [CNA04])
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal ([CNA02], [CNA04]).
P.C.B
GND
Ch 1
Ch 3
*c
*c
*c
*d
Ch 2
CNA02
CNA04
connected unit
*c Select very low current use contacts (usable at DC12V, DC1mA or less).
*d The wiring is different from Apply voltage terminals. Be suf
fi
ciently careful when wiring.
When connected to Dry contact terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
9377773098-01_IM.indb 11
9377773098-01_IM.indb 11
7/12/2012 3:05:26 PM
7/12/2012 3:05:26 PM
Содержание ASHE07GACH
Страница 17: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 29 PM 7 12 2012 3 05 29 PM...
Страница 33: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 36 PM 7 12 2012 3 05 36 PM...
Страница 49: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 43 PM 7 12 2012 3 05 43 PM...
Страница 65: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 51 PM 7 12 2012 3 05 51 PM...
Страница 81: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 58 PM 7 12 2012 3 05 58 PM...
Страница 97: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 06 06 PM 7 12 2012 3 06 06 PM...
Страница 113: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 06 14 PM 7 12 2012 3 06 14 PM...
Страница 129: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 06 22 PM 7 12 2012 3 06 22 PM...