En-9
Example
If 4 indoor units are connected.
RC AD SW
0
RC AD SW
1
RC AD SW
2
RC AD SW
3
Indoor unit
Remote
controller
Indoor unit
Indoor unit
Indoor unit
RC AD SW
0
1
2
3
4
5
6
7
Address
0
1
2
3
4
5
6
7
RC AD SW
8
9
A
B
C
D
E
F
Address
8
9
10
11
12
13
14
15
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting “0”
Since the remote controller address settings are automatically con
fi
gured, you do not
need to con
fi
gure them.
If
con
fi
guring manually, it is necessary to con
fi
gure both the indoor unit and the
remote controller. For details, please refer to the remote controller manual.
6.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
A B C D
A B C D
Indoor
unit
Remote
controller
Confusion
Code change
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2 referring to the Table B.
ON
OFF
DIP switch (SET 3)
Controller PCB
SW1
SW2
SW3
SW4
SET 3
Table B
Custom code
A (Factory setting)
B
C
D
DIP switch SET 3
SW1
OFF
ON
OFF
ON
DIP switch SET 3
SW2
OFF
OFF
ON
ON
6.3. Switching the upper limit of cooling temperature
This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System
controller
• Service
tool
• Web monitoring tool
DIP switch setting
Set the DIP switch SET 4 SW3 referring to the Table C.
ON
OFF
DIP switch (SET 4)
Controller PCB
SW1
SW2
SW3
SW4
SET 4
Table C
DIP switch SET 4 SW3
Cooling temperature setting range
OFF (Factory setting)
Standard (18 to 30 °C)
ON
Extension (18 to 32 °C)
NOTE :
Please do not make a standard setup and an extension setup intermingled in remote
controller group.
6.4. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to “6.1. Setting the address” for indoor unit address and refrigerant circuit ad-
dress settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting number Default
Details
Filter
indicator
interval
11
00
Default
○
Adjust the
fi
lter cleaning interval noti
fi
ca-
tion. If the noti
fi
cation is too early, change
to setting 01. If the noti
fi
cation is too late,
change to setting 02.
01
Longer
02
Shorter
Filter
indicator
action
13
00
Enable
○
Enable or disable the
fi
lter indicator. Set-
ting 02 is for use with a central remote
controller.
01
Disable
02
Display only
on central
remote
controller
Cool air
temperature
trigger
30
00
Default
○
Adjust the cool air trigger temperature. To
lower the trigger temperature, use setting
01. To raise the trigger temperature, use
setting 02.
01
Adjust (1)
02
Adjust (2)
Heat air
temperature
trigger
31
00
Default
○
Adjust the heat air trigger temperature. To
lower the trigger temperature by 6 degrees C,
use setting 01. To lower the trigger tempera-
ture by 4 degrees C, use setting 02. To raise
the trigger temperature, use setting 03.
01
Adjust (1)
02
Adjust (2)
03
Adjust (3)
Auto
restart
40
00
Enable
Enable or disable automatic system
restart after a power outage.
01
Disable
○
Cool Air
Preven-
tion
43
00
Super low
○
Restrain the cold air
fl
ow with making the
air
fl
ow lower when starting heating op-
eration. To correspond to the ventilation,
set to 01.
01
Follow the
setting on
the remote
controller
9377773098-01_IM.indb 9
9377773098-01_IM.indb 9
7/12/2012 3:05:25 PM
7/12/2012 3:05:25 PM
Содержание ASHE07GACH
Страница 17: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 29 PM 7 12 2012 3 05 29 PM...
Страница 33: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 36 PM 7 12 2012 3 05 36 PM...
Страница 49: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 43 PM 7 12 2012 3 05 43 PM...
Страница 65: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 51 PM 7 12 2012 3 05 51 PM...
Страница 81: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 58 PM 7 12 2012 3 05 58 PM...
Страница 97: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 06 06 PM 7 12 2012 3 06 06 PM...
Страница 113: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 06 14 PM 7 12 2012 3 06 14 PM...
Страница 129: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 06 22 PM 7 12 2012 3 06 22 PM...