OUTDOOR UNIT Error Method:
High Pressure Abnormal
OK
OK
OK
OK
1. 3-way valve not opened 2. Outdoor unit fan operation defective, foreign matter at heat
exchanger, excessive ambient temperature rise 3. Check valve clogged
4. EEV defective, strainer clogged 5. Solenoid valve defective
6. Discharge pressure sensor defective 7. Refrigerant overcharged
Judgment from value sensed by discharge
pressure sensor
"Protection stop by "discharge pressure 4.00MPa during operation of any
compressor"" generated 3 times within 60 minutes
EEV operation check
Check of strainers before and after EEV
Check Point 4 : Check the EEV, strainer (indoor unit)
No foreign matter in air passage?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by effect of other heat sources?
Discharged air not sucked in?
Check Point 2 : Check the outdoor unit fan operation,
heat exchanger, ambient temperature
Discharge pressure sensor characteristics check
* For the characteristics of the discharge pressure sensor, refer to
"Service Parts Information".
Check Point 6 :Check the discharge pressure sensor
Check Point 7 : Check the refrigerant amount
Refrigerant charged amount check
Check Point 5 : Check the solenoid valve (SV2)
Solenoid valve operation check
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. A4. 1
Error Code : A4
04-53
<Cooling operation>
OK
<Heating operation>
Check Point 1 : Check if 3-way valve(liquid side) is open.
If the 3-way valve(liquid side) was closed, open the
3-way valve(liquid side) and check operation.
Check Point 1 : Check if 3-way valve(gas side) is open.
If the 3-way valve(gas side) was closed, open the
3-way valve(gas side) and check operation.
OK
OK
Forecast of Cause :
Trouble shooting 43
Indicate or Display:
Detective Actuators:
Detective details:
Refer to "Service Parts Information".
Refer to "Service Parts Information".
EEV(EEV 1) open?
Strainer clogging check. (before EEV)
Refer to "Service Parts Information".
Check Point 3 : Check the EEV, strainer
Содержание ARXB07LALH
Страница 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Страница 2: ......
Страница 6: ......
Страница 7: ...1 TEST RUN...
Страница 8: ......
Страница 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Страница 28: ......
Страница 42: ......
Страница 43: ...3 INDOOR UNIT OPERATION...
Страница 44: ......
Страница 63: ...4 TROUBLE SHOOTING...
Страница 74: ......
Страница 171: ...5 APPENDING DATA UNIT...
Страница 172: ......
Страница 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Страница 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Страница 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Страница 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Страница 178: ...05 06 MODEL ARXB45LATH...
Страница 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Страница 180: ...MODELS ARXC36 45LATH 05 08...
Страница 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Страница 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Страница 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Страница 184: ...MODELS AS A07 09 12 14LACH 05 12...
Страница 185: ...MODELS AS E07 09 12 14LACH 05 13...
Страница 186: ...MODELS AS A18 24 30LACH 05 14...
Страница 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Страница 192: ......
Страница 193: ...6 DISASSEMBLY PROCESS...
Страница 194: ......