2-6 PROTECTIVE FUNCTION
02-11
2-6-1 Protective Function List
Protective Function
Detect Parts
Operating Condition
Operation
Discharge Temp
Protection 1
Discharge Temp
Thermistor
Discharge Temp
Protection 2
Discharge Temp
Thermistor
High Pressure
Protection 1
High Pressure
Sensor
High Pressure
Protection 4
High Pressure
Sensor
COOL HEAT
<Starting conditions>
3 minutes have elapsed since the start of operation and
(discharge temperature 100°C or suction SH 10°C accumulated time
30 minutes)
<Reset conditions>
Discharge temperature 95°C and suctionSH 7°C
EEV of operating indoor unit gradually opened
<Starting conditions>
Cooling: Discharge temperature 95°C
Heating: Discharge temperature 102°C
<Reset conditions>
Discharge temperature 90°C
Discharge temperature 97°C
EEV2 + 30pls/30 secs
Discharge Temp
Protection 4
Discharge Temp
Thermistor
< starting condition>
Discharge temperature 105°C
<Pattern reset condition>
Discharge temperature 100°C
Compressor speed -6rps every 30 secs
Speed rise prohibited,
when discharge temperature becomes lower
than 105 , prohibit the rotational speed rise
of the compressor.
Discharge Temp
Protection 5
Discharge Temp
Thermistor
<Starting conditions>
Discharge temperature 95°C and EEV1=500pls
<Reset conditions>
2 minutes have elapsed and
(discharge temperature 90°C or EEV1 400pls)
Expansion valve of stopped indoor unit gradually
opened
(upper limit 200pls)
Discharge Temp
Protection Stop
Discharge Temp
Thermistor
<Pattern starting condition>
Discharge temperature fixed value (115°C)
<Pattern reset condition>
3 minutes have elapsed and discharge temperature 80°C
Compressor stopped
<Pattern starting condition>
Pattern generated 2 times within 40 minutes
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again
Compressor stopped
(permanent stop)
Error display
<Starting conditions>
COMP < 25 rps ---- HP 3.3 MPa
25 rps COMP < 30 rps ---- HP 3.5 MPa
30 rps COMP
<Reset conditions>
Fixed time has elapsed and Fixed time when SV2: ON 30 secs
COMP < 25 rps ---- HP 3.0 MPa
25 rps COMP < 30 rps ---- HP 3.2 MPa
30 rps COMP
SV2 ON
High Pressure
Protection 2
High Pressure
Sensor
<Starting conditions>
COMP 25 rps ---- HP 3.5 MPa
COMP < 25 rps ---- HP 3.3 MPa
<Reset conditions>
3 minutes have elapsed and high-pressure 2.80MPa
SV2 ON
High Pressure
Protection 3
High Pressure
Sensor
<Starting conditions>
Fixed time has elapsed and high-pressure 3.50MPa
(* Fixed time at start of operation: 10 secs, after operation execution: 20 secs)
<Reset conditions>
Operation (fan speed 1 step increase) complete
Fan speed 1 step increase
<Pattern starting condition>
High-pressure 3.30MPa
<Pattern starting condition>
High-pressure 3.50MPa
<Pattern reset condition>
High-pressure 3.2MPa
<Pattern reset condition>
High-pressure 3.5MPa
Fan speed lowered/every 30 secs
Fan lowest speed
Upper 270 rpm
Lower 250 rpm
DISPLAY
P1
EA11
High Pressure
Protection 5
High Pressure
Sensor
Abnormal High
Pressure Protection
Control
High Pressure
Sensor
<Starting conditions>
High-pressure 3.20MPa
Compressor capacity lowered/every 15 secs
<Pattern starting condition>
COMP < 30 rps ---- HP 3.18 MPa
COMP 30 rps ---- HP 3.68 MPa
<Pattern reset condition>
After 25 seconds have elapsed and,
COMP < 30 rps ---- HP 3.1 MPa
COMP 30 rps ---- HP 3.6 MPa
Compressor capacity rise prohibited
<Reset conditions>
High-pressure 3.20MPa
<Pattern starting condition>
COMP 30 rps ---- HP 3.3 MPa
COMP 30 rps ---- HP 3.8 MPa
<Pattern reset condition>
After 25 seconds have elapsed and,
COMP 30 rps ---- HP 3.18 MPa
COMP 30 rps ---- HP 3.68 MPa
Compressor capacity lowered every 30 secs
---- HP 3.8 MPa
---- HP 3.5 MPa
Содержание ARXB07LALH
Страница 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Страница 2: ......
Страница 6: ......
Страница 7: ...1 TEST RUN...
Страница 8: ......
Страница 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Страница 28: ......
Страница 42: ......
Страница 43: ...3 INDOOR UNIT OPERATION...
Страница 44: ......
Страница 63: ...4 TROUBLE SHOOTING...
Страница 74: ......
Страница 171: ...5 APPENDING DATA UNIT...
Страница 172: ......
Страница 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Страница 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Страница 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Страница 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Страница 178: ...05 06 MODEL ARXB45LATH...
Страница 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Страница 180: ...MODELS ARXC36 45LATH 05 08...
Страница 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Страница 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Страница 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Страница 184: ...MODELS AS A07 09 12 14LACH 05 12...
Страница 185: ...MODELS AS E07 09 12 14LACH 05 13...
Страница 186: ...MODELS AS A18 24 30LACH 05 14...
Страница 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Страница 192: ......
Страница 193: ...6 DISASSEMBLY PROCESS...
Страница 194: ......