Trip Detection
OK
OK
1. Outdoor unit fan operation defective, foreign matter on hear exchanger, excessive rise of ambient
temperature
2. Inverter PCB defective
3. Inverter compressor defective (lock, winding short)
4. SV2 Coil Abnormal
Inverter PCB
Inverter Compressor
"Protection stop by "overcurrent generation after inverter compressor start
processing completed'''' generated consecutively 5 times.
* The number of generations is reset if protection stop is not generated again
within 40 seconds after restarting.
No obstructions in air passages?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by the effect of other heat sources?
Discharged air not sucked in?
Check Point 3 : Check the Inverter compressor
Check Inverter compressor
Check Point 2 : Check the Inverter PCB
Inverter PCB check (Refer to Service Parts Information )
Check Point 1 : Check the outdoor unit fan operation, heat exchanger, ambient temperature
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. 94. 1
Error Code : 94
04-45
Trouble shooting 35
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
(Refer to Service Parts Information )
SV 2 coil
Check Point 4: Check the SV2, Coil
Check the connector of SV2 connected on the Main PCB surely.
Check the Coil installed on the Valve surely ( Fixed condition, direction, depth)
Check the resistance of wires ( Not open circuit )
Check the valve are operating surely
OK
Содержание ARXB07LALH
Страница 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Страница 2: ......
Страница 6: ......
Страница 7: ...1 TEST RUN...
Страница 8: ......
Страница 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Страница 28: ......
Страница 42: ......
Страница 43: ...3 INDOOR UNIT OPERATION...
Страница 44: ......
Страница 63: ...4 TROUBLE SHOOTING...
Страница 74: ......
Страница 171: ...5 APPENDING DATA UNIT...
Страница 172: ......
Страница 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Страница 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Страница 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Страница 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Страница 178: ...05 06 MODEL ARXB45LATH...
Страница 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Страница 180: ...MODELS ARXC36 45LATH 05 08...
Страница 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Страница 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Страница 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Страница 184: ...MODELS AS A07 09 12 14LACH 05 12...
Страница 185: ...MODELS AS E07 09 12 14LACH 05 13...
Страница 186: ...MODELS AS A18 24 30LACH 05 14...
Страница 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Страница 192: ......
Страница 193: ...6 DISASSEMBLY PROCESS...
Страница 194: ......