Printed Documentation
26
Note:
This must be a SELV port of an EN 60950 approved product.
Run the E1 cables from the AC shelf to the allocated positions on the DDF. In partial
equipped installations it may be appropriate to run enough cables to cater for a complete rack
of equipment. This reduces the need to disturb original installation when adding additional
equipment.
Feed the E1 cables through the top hole on the most convenient side of the rack, and down
the front of the rack. Identify and label each cable at both ends as well as the DDF/Backhaul
positions. Terminate all cables with RJ45 plugs and fit adapter 303-1113-900 (See RJ45
terminations below) or use D-type connectors (See D-type terminations below) at the rack
.Terminate as appropriate at the DDF.
RJ45 Terminations
Terminate all cables with RJ45 connectors at the rack and as appropriate at the DDF.
RJ45 connector termination
Fit the RJ45 adapter 303-1113-900 (Slots 4,5 and 6) and 303-1112-900 (slots 7-14) and
secure to the Backplane using screws in the top and bottom holes of the adapter.
D-Type Terminations:
Terminate all cables with 25 pin D-type connectors (120Ohm )
according to the tables below or fit RJ45 adapter to the D-Type Plugs on the AC Interface
Panel. .
Note:
On D-Type connectors the screen connects to pin 13
Содержание AS4000
Страница 2: ......
Страница 6: ...Printed Documentation 2 ...
Страница 14: ...Printed Documentation 10 ...
Страница 16: ...Printed Documentation 12 ...
Страница 27: ...Installation 23 Typical 75ohm DDF Layout ...
Страница 28: ...Printed Documentation 24 ...
Страница 38: ...Printed Documentation 34 AC Rack Labeling The racks should be labelled as shown below Access Concentrator Rack ...
Страница 39: ...Installation 35 Interface Connections This page contains miscellaneous interface and connector details ...
Страница 41: ...Installation 37 ...
Страница 42: ...Printed Documentation 38 BNC Terminations to Coax ...
Страница 43: ...Installation 39 Type 43 Terminations to Coax ...
Страница 44: ...Printed Documentation 40 ...
Страница 52: ...Printed Documentation 48 ...
Страница 68: ...Printed Documentation 64 ...
Страница 69: ...Installation 65 Interface Connections This page contains miscellaneous interface and connector details ...
Страница 71: ...Installation 67 ...
Страница 72: ...Printed Documentation 68 CT Rack Labelling Central Terminal Rack ...
Страница 73: ...Installation 69 BNC Terminations to Coax ...
Страница 74: ...Printed Documentation 70 Type 43 Terminations to Coax ...
Страница 75: ...Installation 71 ...
Страница 78: ...Printed Documentation 74 Card Insertion DA Rack Card Insertion Expansion Rack ...
Страница 110: ...Printed Documentation 106 ...
Страница 112: ...Printed Documentation 108 Combiner Shelf PSU ...
Страница 133: ...Setup and Test 129 ...
Страница 151: ...Setup and Test 147 11 From the AS4020 front panel exit commissioning mode by selecting RF Commissioning Off ...
Страница 163: ...Setup and Test 159 ...
Страница 166: ......
Страница 170: ...Printed Documentation 166 ...
Страница 176: ...Printed Documentation 172 ...
Страница 192: ......