Terminate the battery feed and return cables at the isolator/fuse positions, and ensure that
the AC rack is isolated until the commencement of commissioning tests.
DC Power
The cables for the negative DC battery feeds, the 0V returns and the Rack Ground are
detailed in. Should local requirements specify otherwise, it is acceptable for cables of other
colours to be used, however, under no circumstances should the cable sizes be less than that
specified in. The length of the cable supplied will be detailed in the site survey. Separate DC
sources are desirable for maximum protection.
Function
Colour
Min. Cable Size
Negative Battery Feed -36V
to -60V DC
Blue
10 AWG; 6.0mm
2
Zero Volt Positive Battery
Return
Black
10 AWG; 6.0mm
2
Rack Ground
Green
/
Yellow
8AWG; 10.0mm
2
DC Power Cables.
This equipment requires a negative Supply. Ensure that the +ve volt line is connected
to ground or that the supply is floating. The
–
ve battery feed should not be connected to
ground or zero volts under any circumstances.
The maximum DC input should not exceed 60 Volts. Voltages in excess of this are
considered hazardous.
Note 1:
Do not insert fuses until instructed to do so in the commissioning stage of installation.
Note 2:
If the equipment is installed according to EN 60950 §1.7.9, there should be available
a single disconnect device that isolates the whole equipment., A double-pole external
isolating switch should be provided to isolate the two supplies and should be wall mounted in
the locale of the rack. A label should be included on the unit to direct the user to use the
external isolator for isolation.
The Access Concentrator and Central Terminal Shelves are designed to operate from a -48V
DC supply. In installations where the nominal supply voltage is +24V DC a DC to DC
converter is needed to provide the -48V supply see the schematic diagram below. The DC to
DC converter must be rated at 20 amps or greater at -48V DC
Содержание AS4000
Страница 2: ......
Страница 6: ...Printed Documentation 2 ...
Страница 14: ...Printed Documentation 10 ...
Страница 16: ...Printed Documentation 12 ...
Страница 27: ...Installation 23 Typical 75ohm DDF Layout ...
Страница 28: ...Printed Documentation 24 ...
Страница 38: ...Printed Documentation 34 AC Rack Labeling The racks should be labelled as shown below Access Concentrator Rack ...
Страница 39: ...Installation 35 Interface Connections This page contains miscellaneous interface and connector details ...
Страница 41: ...Installation 37 ...
Страница 42: ...Printed Documentation 38 BNC Terminations to Coax ...
Страница 43: ...Installation 39 Type 43 Terminations to Coax ...
Страница 44: ...Printed Documentation 40 ...
Страница 52: ...Printed Documentation 48 ...
Страница 68: ...Printed Documentation 64 ...
Страница 69: ...Installation 65 Interface Connections This page contains miscellaneous interface and connector details ...
Страница 71: ...Installation 67 ...
Страница 72: ...Printed Documentation 68 CT Rack Labelling Central Terminal Rack ...
Страница 73: ...Installation 69 BNC Terminations to Coax ...
Страница 74: ...Printed Documentation 70 Type 43 Terminations to Coax ...
Страница 75: ...Installation 71 ...
Страница 78: ...Printed Documentation 74 Card Insertion DA Rack Card Insertion Expansion Rack ...
Страница 110: ...Printed Documentation 106 ...
Страница 112: ...Printed Documentation 108 Combiner Shelf PSU ...
Страница 133: ...Setup and Test 129 ...
Страница 151: ...Setup and Test 147 11 From the AS4020 front panel exit commissioning mode by selecting RF Commissioning Off ...
Страница 163: ...Setup and Test 159 ...
Страница 166: ......
Страница 170: ...Printed Documentation 166 ...
Страница 176: ...Printed Documentation 172 ...
Страница 192: ......