TECHNICAL PARAMETERS
INSTALLATION
8
Number of phases/Voltage [V]/Current [A]/Power consumption [W]
Type
Maximum
air flow
[m
3
/h]
Intake
filter
class
Exhaust
filter
class
Frequency
[Hz]
Unit without
heaters
EPRH
EPOH
WPOH
EPRH-EPOH
EPRH-WPOH Weight*
[kg]
Susurro 400
400
F7
G4
50
1 / 230 / 2.7 / 340 1 / 230 / 9.22 / 1840 1 / 230 / 9.22 / 1840 1 / 230 / 2.7 / 340 1 / 230 / 15.74 / 3340 1 / 230 / 9.22/ 1840
95
Susurro 700
700
F7
G4
50
1 / 230 / 2.7/ 340 1 / 230 / 11.4 / 2340 1 / 230 / 12.48 / 2590 1 / 230 / 2.7 / 340 3 / 400 / 9.78 / 4590 1 / 230 / 11.4 / 2340
130
Susurro 1000
1000
F7
G4
50
1 / 230 / 5.0 / 700 3 / 400 / 7.5 / 3770 3 / 400 / 9.33 / 3770 1 / 230 / 5.0 / 700 3 / 400 / 11.83 / 6770 3 / 400 / 7.5 / 3770
152
* Given weight refers to the heaviest unit for each model
EPRH - electric pre-heater
EPOH - electric post-heater
WPOH - water post-heater
CHOOSING THE PLACE
The project of the ventilation system must be prepared by a HVAC designer.
TECHNICAL INFORMATION
The unit must be operated in a closed, dry place with a range of temperatures of
+5°C to +40°C.
+5°C
+40°C
The filtered air must have a temperature ranging from -15°C to +40°C and a relative humidity of up to 90%.
If air at a temperature lower than -15°C is to be sucked, the unit can work in the anti-freeze mode or may switch itself off
to prevent damages to important components.
-20 °C
+40 °C
max. 90%
15 °C
INSTRUCTION MANUAL
Susurr