CONTROL
Check the following before switching on the unit for the first time:
•
That the unit is properly closed and all the outlets are connected to the ductwork.
•
That the electric connection matches the diagram, including earthing and protection of external circuits.
•
That all the electric components are properly connected.
•
That the condensate drain is connected to the sewage
•
That the installation corresponds to the instructions in the manual.
•
That no tools or objects that may damage the unit have been left inside.
•
That the filters are clean
CAUTION!
•
Alterations and changes to the internal connections of the unit are forbidden and may result in the loss of warranty.
•
We recommend the use of accessories provided by our company. Contact your supplier in case of doubts with the use of
non-original accessories.
INITIAL COMMISSIONING
•
After connecting the unit, the display lights up and the data
is loaded. The service data begins to load. Once it has fully
loaded, the unit is ready for start-up.
•
The remote control has a touch-screen – the unit is controlled
touching the symbols on the screen.
Switching the unit to
stand-by mode
Activate boost mode
Unit's time switch
Displays current temperature,
ventilation rate, CO2 concentration,
ventilation date and mode
Ventilation rate settings
Required temperature
settings
Password lock
Detailed information
on ventilation status
Unit’s settings
(Service menu)
Start-up:
INFORMATION ON THE VENTILATION
STATUS
Back
This screen shows the status of the unit and the values of
the sensors::
•
Current air flow of both fans
•
Inlet and exhaust air temperature
•
Status of the heat exchanger bypass
•
Performance of the electric preheating and reheating
•
Values of the connected air quality sensor
Information on
the type of unit
Occupancy mode active
The timer is active
The cooling is active
(with a graphic
indication of the
remaining time)
30%
30%
17