G-58
Z-106164_EN ● 00
A
dditionAl
i
nformAtion
for
the
i
nstAller
Top menu
Pgm No.
Submenu 1
Submenu 2
Default
Setting
Domestic Hot
Water
1610
»
Nominal setpoint
70°C
(5 pages)
1612
»
Reduced setpoint
40°C
1620
»
Release
24h/day
Time programs HCs
Time program 4/DHW
24h/day
1630
»
Charging priority
Absolute
Shifting
None
MC shifting, PC
absolute
1640
»
Legionella function
Off
Periodically
Fixed weekday
1641
»
Legionella funct periodically
1 to 7
1642
»
Legionella funct weekday
Monday to Sunday
1644
»
Legionella funct time
--:--
1645
»
Legionella funct setpoint
65°C
1646
»
Legionella funct duration
30 min
1647
»
Legionella funct circ pump
Off
On
On
1660
»
Circulating pump release
Time program 3/HCP
DHW release
Time program 4/DHW
Time program 5
1661
»
Circulating pump cycling
Off
On
1663
»
Circulation setpoint
45°C
1680
»
Optg mode changeover
Off
On
Heat pump
2855
»
Switch off temp max HC
2909
»
Release below outside temp
2910
»
Release above outside temp
2911
»
For forced buffer charging
Release
2912
»
Full charging buffer
On
Supplementary
source (Boiler)
3690
»
Setpoint incr main source
0°C
3692
»
With DHW charging
Locked
Substitute
Complement
Instantly
First
Alone
Alone
3700
»
Release below outside temp
8°C
3701
»
Release above outside temp
-
3710
»
Setpoint min
40°C
3711
»
Setpoint max
80°C
3720
»
Switching integral
50°C
3722
»
Swiching diff off
15°C
3723
»
Locking time
20 min
Buffer storage
tank
4709
»
Forced charg setp heat min
45°C
4710
»
Forced charg setp heat max
45°C
4711
»
Forced charging time
12:00
4712
»
Forced charg duration max
1 h
4750
»
Charging temp max
60°C
Содержание TMU 500
Страница 45: ...G 45 Z 106164_EN 00 Product Installation Fig 23 Wiring heat pump circulating pump Fig 24 TMU wiring Boiler...
Страница 65: ...G 65 Z 106164_EN 00 NOTES...
Страница 66: ...G 66 Z 106164_EN 00 NOTES...
Страница 67: ...G 67 Z 106164_EN 00 NOTES...
Страница 68: ...www myaic eu AIC Europe B V Graafschap Hornelaan 163A NL 6001 AC Weert The Netherlands...