
G-49
Z-106164_EN ● 00
C
ommissioning
Functions
Domestic Hot Water
1612 - Reduced setpoint (40°C)
1620 - Release (
24h/day
/ Time programs HCs / Time program 4/DHW)
1630 - Charging priority (Absolute / Shifting / None /
MC shifting, PC absolute
)
1640 - Legionella function (Off / Periodically /
Fixed weekday
)
1645 - Legionella function setpoint (65°C)
1641 - Legionella function periodically (3)
1642 - Legionella function weekday (Monday / Tuesday / Wednesday.../ Sunday)
Skip
Skip
Redo
Redo
Continue
Continue
System setup
LPB system
6600 - Device address (
1
....16)
6601 - Segment address (
0
...14)
6640 - Clock mode (
Autonomously
/ Slave without remote setting / Slave with remote
setting / Master)
Modbus
6651 - Slave address (
unused
(0) ... 247)
6652 - Baud rate (19 200)
6653 - Parity (Even)
6654 - Stop bit (
1
/ 2)
Secure
See next page
Содержание TMU 500
Страница 45: ...G 45 Z 106164_EN 00 Product Installation Fig 23 Wiring heat pump circulating pump Fig 24 TMU wiring Boiler...
Страница 65: ...G 65 Z 106164_EN 00 NOTES...
Страница 66: ...G 66 Z 106164_EN 00 NOTES...
Страница 67: ...G 67 Z 106164_EN 00 NOTES...
Страница 68: ...www myaic eu AIC Europe B V Graafschap Hornelaan 163A NL 6001 AC Weert The Netherlands...