AC Mains Connections
5 kW, 208 VAC and 400 VAC,
phase balancing scheme
10 kW, 208 VAC and 400 VAC,
phase balancing scheme
Power Cables
An AC mains power cable is not provided with the unit. Refer to the following table for the maximum current capacity
requirements for each cable conductor. If required by local electrical codes, install a fuse or circuit breaker between the
ac mains and the unit. Refer to the following table for current ratings.
The cable cross-section must be suitable for the maximum input current of the instru-
ment. The ground cable must be of the same cross-section as the phase cables.
Safety agency requirements dictate that there must be a way to physically disconnect the AC mains
cable from the unit. The detachable connection plug (see below) may be used as the emergency dis-
connection device. Removing the connector will disconnect AC input power to the unit. Ensure that
the connector is accessible.
Unit Rating
L1 I
max
L2 I
max
L3 I
max
5 kW - 208 Vac
NA
32 A
32 A
5 kW - 400 Vac
NA
16 A
16 A
10 kW - 208 Vac
56 A
32 A
32 A
10 kW - 400 Vac
28 A
16 A
16 A
15 kW - 208 Vac
56 A
56 A
56 A
15 kW - 400 Vac
28 A
28 A
28 A
Keep the AC mains cables as short as possible. The longer the cable, the greater the voltage loss due to cable resistance.
The safety ground wire must be green. Other colors, shown below, are for illustration purposes.
For heavier AC mains cables, it may be necessary to install a strain relief to reduce weight and eliminate movement at
the cable connector. If possible, attach the strain relief to the side of the instrument rack. Allow sufficient movement at
the cable connector so that the cable connector can be removed from the instrument.
Agilent N8900 Series Operating and Service Guide
27
Содержание N8900 series
Страница 1: ...Agilent N8900 Series Autoranging System DC Power Supply Operating and Service Guide...
Страница 36: ...Multiple Unit Connections Agilent N8900 Series Operating and Service Guide 35...
Страница 104: ...Status Tutorial Status Diagram Agilent N8900 Series Operating and Service Guide 103...
Страница 117: ...Service and Maintenance Service and Maintenance Pending 116 Agilent N8900 Series Operating and Service Guide...
Страница 118: ...Verification and Calibration Verification and Calibration Pending Agilent N8900 Series Operating and Service Guide 117...
Страница 119: ......