11.3 EMC categories: first and second environments
The SE-24 servo controller, when correctly installed and connected, complies with the
regulations of the corresponding product norms EN 61000-6-2 and EN-61000-6-4. In
these norms, reference is no longer made to “limiting value classes”, but to so called
environments.
The “first” environment covers electricity networks servicing residential
buildings, the second environment covers electricity networks exclusively servicing
industrial enterprises.
11.4 Connection between SE-24 and motor
The following wiring guidelines should be followed for connecting the servo controller
to the motor:
▪
Only use shielded cables.
▪
Use separate cables for the motor phases and the angle transmitter.
Optional: Use a combined cable for the motor and the angle transmitter with
separate shielding.
▪
Connect all (outer) shields with the SE-24 housing.
▪
Connect the shield of the motor cable with the motor housing.
▪
Ensure a “good” PE connection between the motor and the SE-24.
NOTE
A “good” PE connection has a small impedance even at high
interference frequencies.