AtteNtIoN
The choice and the installation of
components external to the ANL
°|H èup to the installer, who must
operate according to the rules
of good technical design and in
compliance with the regulations in
force in the country of destination.
AtteNtIoN
The hydraulic pipes connecting to
the machine must be properly si-
zed to the actual flow of water re-
quired by the system in operation.
The water flow to the exchanger
must always be constant.
AtteNtIoN
Carefully wash the plant, before
connecting the unit. This allows
cleaning to remove any residue
such as weld spatter, slag, rust or
other impurities from the pipes.
These substances may otherwise
accumulate in and cause a machi-
ne malfunction. The connecting
pipes should be supported so as
not to weigh, with their weight on
the unit.
PH
6-8
Electric conductivity
less than 200 mV/cm (25°C)
Chloride ions
less than 50 ppm
Sulphuric acid ions
less than 50 ppm
Total iron
less than 0,3 ppm
Alkalinity M
less than 50 ppm
Total hardness
less than 50 ppm
Sulphur ions
none
ammonia ions
None
Silicone ions
less than 30 ppm
20.2.
CIrCUITO IDrAULICO InTErnO ED ESTErnO AD AnL “HP"
HYDrAULIC
CoMPoNeNtS
ANL
HYDrAULIC CoMPoNeNtS
SUggeSteD eXterNAL UNIt
3
PD
4
4
2
12
5
5
1
8
13
7
11
6
8
9
10
11
13
8
7
CoMPoNeNtS SUPPLIeD AS StANDArDS
1
Water filter
2
Pressure switch
3
Plate exchanger
4
porbe water temperature (in/oUT)
6
Safety valve
7
Expansion tank
8
air Vent
12
Pump
Not SUggeSteD CoMPoNeNtS ProVIDeD to LoAD INStALLer
5
anti vibration joints
7
Expansion tank (if necessary)
9
Storage tank
10
Drain cock
11
Ball Stop
13
Manometer