eN
1205. 6755517_02
23
16.
SoUND DAtA
S
ound power
Aermec determines sound power values in
agreement with the 9614 Standard, in com-
pliance with that requested by Eurovent cer-
tification.
Sound Pressure
Sound pressure measured in free field condi-
tions with reflective surface (directivity factor
Q=2) at 10mt distance from external surface
of unit, in compliance with ISO 3744 regula-
tions.
KEY
- Water input temperature
12 °C
- Temperature of produced water 7 °C
- External air temperature
35 °C
ANL
Total sound levels
Octave band [Hz]
Pow.
dB(A)
Pressure.
125
250
500
1000
2000
4000
8000
dB(A)
10 m
dB(A)
1 m
Sound power for centre of band [dB] frequency
100
76.0
44.0
58.0
61.2
66.0
71.4
72.0
68.9
60.5
48.6
150
77.0
45.0
59.0
62.4
67.3
72.2
72.7
69.7
61.5
49.6
17.
PArAMeter CALIBrAtIoN oF
SAFetY AND CoNtroL
CoNtroL PArAMeterS
ANL
min.
standard
max.
Cooling set point
°C
4
7
18
Heating set point
°C
35
45
50
Defrosting mode
°C
-9
3
4
Total differential
°C
3
5
10
Autostart
auto
CALIBrAtIoN tHerMoMAgNetIC ANL60Hz
Models 60Hz
Compressors magnet
circuit breakers
Pumps magnet
circuit breakers
Fan magnet
circuit breakers
anl100Ha 220V
19,0 A
3,5 A
Fixed 6A (also for auxiliary)
anl100Ha 460V
10,0 A
1,8 A
Fixed 6A (also for auxiliary)
anl150Ha 220V
23,0 A
5,7 A
Fixed 6A (also for auxiliary)
anl150Ha 460V
12,5 A
3,0 A
Fixed 6A (also for auxiliary)
100H
150H
SAFETY AND CONTROL COMPONENTS ELECTRIC DATA
High pressure pressure switch
bar
42
42
Low pressure pressure switch
cold
bar
4
4
PdC
bar
2
2
High pressure transducer
bar
40
40
Содержание ANL 100HA
Страница 2: ......
Страница 5: ......
Страница 30: ...eN 1205 6755517_02 30 23 HYDrAULIC CoNNeCtIoNS 102 mm 4 0 in 413 mm 16 3 in IN 1 OUT 1 ...