teCHNICAL DAtA
teCHNICAL DAtA
MoDeLS
Power SUPPLY
M.U.
ANL100
ANL150
CooLINg MoDe
Cooling capacity
Alls
Alls
Tons
6,57
8,16
Total input power
H
Alls
kW
8,24
9,48
HP-HA
Alls
kW
8,99
10,98
Water flow rate
Alls
Alls
gpm
16
20
Evaporator pressure drops
H
-
psi
3,80
3,52
Filter pressure drop
H
-
psi
0,55
0,84
Total pressure drop
H
-
psi
4,35
4,36
Useful head
HP-HA
-
psi
14,65
19,14
HeAtINg MoDe
Heating capacity
Alls
Alls
BTU/h
94755
111850
Total input power
H
Alls
kW
8,29
9,57
HP-HA
Alls
kW
9,04
11,07
Water flow rate
Alls
Alls
gpm
21
25
Evaporator pressure drops
H
-
psi
6,38
5,15
Filter pressure drop
H
-
psi
0,96
1,31
Total pressure drop
H
-
psi
7,34
6,45
Useful head
HP-HA
-
psi
10,44
14,94
eNergY INDeX
EER
H
Alls
W/W
9,58
10,34
HP-HA
Alls
W/W
8,78
8,92
COP
H
Alls
W/W
3,35
3,43
HP-HA
Alls
W/W
3,07
2,96
iplV
Alls
Alls
BTU/W
16,39
17,73
eLeCtrICAL DAtA
Imput current on
COOLING
H
220-3-60
A
31,40
36,70
H
460-3-60
A
17,10
19,64
HP-HA
220-3-60
A
34,26
42,51
HP-HA
460-3-60
A
18,66
22,75
Imput current on
HEATING
H
220-3-60
A
31,59
37,05
H
460-3-60
A
17,21
19,83
HP-HA
220-3-60
A
34,45
42,86
HP-HA
460-3-60
A
18,76
22,93
peak current (lra)
H
220-3-60
A
167,40
192,20
H
460-3-60
A
81,40
94,30
HP-HA
220-3-60
A
171,00
198,40
HP-HA
460-3-60
A
83,40
97,50
MCA
H
220-3-60
A
51,30
60,60
H
460-3-60
A
25,50
31,80
HP-HA
220-3-60
A
54,90
66,80
HP-HA
460-3-60
A
27,50
35,00
MOP
H
220-3-60
A
70,00
80,00
H
460-3-60
A
35,00
45,00
HP-HA
220-3-60
A
75,00
90,00
HP-HA
460-3-60
A
35,00
45,00
HeAtINg (AHrI CoNDItIoNS)
Inlet water temperature
40°C / 104°F
Outlet water temperature
45°C / 113°F
External air temperature
7°C / 44.6°F b.s
6°C / 42.8°F b.u.
CooLINg (AHrI CoNDItIoNS)
Outlet water temperature
6,7°C / 44,6°F
Flow rate
0,043l/s per kW
External temperature
35°C / 95°F
AHrI conditions: leaving water 6,7°C / 44,6°F
flow rate 0,043 l/s per kW (full load)
Load 100% air 35°C / 95°F
Load 75% air 26,7°C / 80,06°F
Load 50% air 18,3°C / 64,94°F
Load 25% air 12,8°C / 55,04°F
SoUND Power
Aermec determines sound power values in agree
-
ment with the 9614-2 Standard.
SoUND PreSSUre
Sound pressure measured in free field conditions
with reflective surface (directivity factor q=2) at
394 in/10mt distance from external surface of unit,
in compliance with ISO 3744 regulations.