APPENDIX H
APPENDIX H
(cont.)
__________________________
H-2. BMS II Controller Standard Holding Register Assignments
The Holding Register address assignments for the BMS II are listed in Table H-2 which follows. Unless
otherwise specified, all Holding Register Menu items are Read/Write (R/W).
Table H-2. BMS II Standard Holding Register Address Mapping
Modbus Data
Address (Hex)
Menu Item
Units and Range
Default/Comments
0x0000
thru
0x0003
(Reserved)
0x0004
Net Header Set
Temp
40 to 220°F
Valid when Hdr Set
Mode=Remote Setpt
and Remote Signal =
Network
0x0005
System Start Temp
32 to 120°F
Default = 70°F
0x0006
System Start Option
0 or 1
0 = Temp Only,
1 = Temp and Load
Default = 0
0x0007
Manual Hdr Set
Temp/Internal Setpt
40 to 220°F
Default = 160°F
0x0008
Bldg Ref Temp
40 to 220°F
Default = 70°F
0x0009
Not Applicable
0x000A
Not Applicable
0x000B
Reset Ratio
0.3 to 3.0
(0.1 increments),
Default = 1.2
(Value x 10)
0x000C
Max Header Temp
40 to 220°F
Default = 200°F
0x000D
Min Header Temp
40 to 220°F
Default = 40°F
0x000E
Start Percent
25 to 100%
Default = 20%
0x000F
Stop Percent
10 to 45%
Default = 16%
0x0010
Integral Gain
0.00 to 9.99 Rep/Min
(in 0.01 increments
Default = 0.15 Rep/Min
(Value x 100)
0x0011
Header Set Mode
0, 1, or 2
0 = Constant Setpt
1 = In/Outdoor Reset
2 = Remote Setpt
Default = 0
(Constant Setpt))
H-5
Содержание BOILER MANAGEMENT SYSTEM II 5R5-384
Страница 8: ......
Страница 12: ......
Страница 16: ...INSTALLATION ...
Страница 17: ...INSTALLATION 2 5 ...
Страница 21: ...INSTALLATION ...
Страница 32: ...OPERATION Figure 3 2 BMS II Menu Structure 3 4 ...
Страница 46: ......
Страница 64: ......
Страница 70: ......
Страница 72: ......
Страница 73: ...APPENDIX E E 1 APPENDIX E _____________________________ BMS II WIRING DIAGRAM ...
Страница 74: ......
Страница 76: ......
Страница 84: ......
Страница 88: ...APPENDIX H H 4 A _ ...
Страница 98: ......