APPENDIX A
APPENDIX A
_____________________________
BMS II MENUS
- Continued
AVAILABLE CHOICES OR LIMITS
MENU LEVEL & OPTION
MINIMUM
MAXIMUM
DEFAULT
RELAY MENU
SYS START TEMP
032°F
120°F
070°F
SYS START OPTION
TEMP ONLY,
TEMP AND LOAD
TEMP ONLY
SYS START INTLK
DISABLED
INTERLOCK 1
INTERLOCK 2
INTERELOCK 1&2
INTERLOCK 1
AUX RELAY OPEN
000%
099%
045%
AUX RELAY CLOSE
100% FIRE RATE,
100% AND OFF
100% AND OFF
FAULT ALRM RELAY
ALL FAULTS,
NO INTERLOCK,
INTERLOCK 2,
INTERLOCK 1
ALL FAULTS
FAULT ALARM BLRS
NO BLR FAULTS,
ALL BLR FAULTS
NO BLR FAULTS
FAULT ALRM CLEAR
AUTOMATIC,
MANUAL RESET
AUTOMATIC
CALIBRATION MENU
HDR SENS OFFSET
-10.0°
10.0°
00.0°
OUTD SENS OFFSET
-10.0°
10.0°
00.0°
4 – 20 MA OFFSET
-10.0
10.0
00.0
RET SENS OFFSET
-10.0°
10.0°
00.0
RAMP UP %/MIN
000
300
020
RAMP DOWN %/MIN
000
300
200
LOAD START PCT
000
100
1
LOAD STOP PCT
000
100
0
RESET DEFAULTS
NO,
YES (DONE If Selected)
NO
A-4
Содержание BOILER MANAGEMENT SYSTEM II 5R5-384
Страница 8: ......
Страница 12: ......
Страница 16: ...INSTALLATION ...
Страница 17: ...INSTALLATION 2 5 ...
Страница 21: ...INSTALLATION ...
Страница 32: ...OPERATION Figure 3 2 BMS II Menu Structure 3 4 ...
Страница 46: ......
Страница 64: ......
Страница 70: ......
Страница 72: ......
Страница 73: ...APPENDIX E E 1 APPENDIX E _____________________________ BMS II WIRING DIAGRAM ...
Страница 74: ......
Страница 76: ......
Страница 84: ......
Страница 88: ...APPENDIX H H 4 A _ ...
Страница 98: ......