APPENDIX A
APPENDIX A
_____________________________
BMS II MENUS
AVAILABLE CHOICES OR LIMITS
MENU LEVEL & OPTION
MINIMUM
MAXIMUM
DEFAULT
OPERATING MENU
HEADER TEMP
40
280
N/A
HEADER SET TEMP
40
220
N/A
OUTSIDE AIR TEMP
-60
180
N/A
PERCENT OF LOAD
0
100
N/A
I/O STATUS
Bit 0 = AUX Relay
Bit 1 = Fault Relay
Bit 2 = Sys Start Relay
Bit 3 = Empty
Bit 4 = Setback
Bit 5 = Interlock 2
Bit 6 = Interlock 1
Bit 7 = Empty
RETURN TEMP
40
280
N/A
SETUP MENU
ENTER PASSWORD
(Level 1 = 159)
(Level 2 = 6817)
0 32000
0
SET MONTH
01
12
SET DATE
01
31
SET YEAR
00
99
SET HOUR
00
23
SET MINUTE
00
59
SET DAY OF WEEK
SUNDAY TO SATURDAY
RS232 MENU
RS232 MODE
MODBUS SLAVE,
NORMAL
MODBUS SLAVE
RS232 BAUDRATE
2400, 4800,
9600, 19200
9600
MODBUS ADDRESS
128
247
128
NETWORK TIMEOUT (Seconds)
005
240
060
MODBUS PASS THRU
DISABLED,
ENABLED
DISABLED
A-1
Содержание BOILER MANAGEMENT SYSTEM II 5R5-384
Страница 8: ......
Страница 12: ......
Страница 16: ...INSTALLATION ...
Страница 17: ...INSTALLATION 2 5 ...
Страница 21: ...INSTALLATION ...
Страница 32: ...OPERATION Figure 3 2 BMS II Menu Structure 3 4 ...
Страница 46: ......
Страница 64: ......
Страница 70: ......
Страница 72: ......
Страница 73: ...APPENDIX E E 1 APPENDIX E _____________________________ BMS II WIRING DIAGRAM ...
Страница 74: ......
Страница 76: ......
Страница 84: ......
Страница 88: ...APPENDIX H H 4 A _ ...
Страница 98: ......