APPENDIX G
APPENDIX G
(cont.)
__________________________
Table G-1. BMS II COMMANDS
– (Continued)
No.
COMMAND
ENTRY RANGE
FACTORY DEFAULT
129 Modbus Pass-Thru
0 = Disabled
1 = Enabled
0 = Disabled
130 Header Temp Deadband
01 to 15°F
05°F
131 Outside Temp Sensor Offset
-10.0°F to 10.0°F
0.0°F
132 Ramp Up %/Min
000 to 300
20
133 Ramp Down %/Min
000 to 300
200
134 Fault Alarm Boilers
No Blr Faults
All Blr faults
No Blr Faults
135 4-20 mA Offset
-1.00 to 1.00 mA
0.0 mA
136 Return Sensor Offset
-10.0 to 10.0°F
0.0°F
137 Load Start Pct
000 to 100
1
138 Load Stop Pct
000 to 100
0
150 I/O Status
00 to 255
Bit 0 = AUX Relay
Bit 1 = Fault Relay
Bit 2 = Sys Start Relay
Bit 3 = Empty
Bit 4 = Setback
Bit 5 = Interlock 2
Bit 6 = Interlock 1
Bit 7 = Empty
151
&
Up
(Reserved For Future Expansion)
Undefined
G-7
Содержание BOILER MANAGEMENT SYSTEM II 5R5-384
Страница 8: ......
Страница 12: ......
Страница 16: ...INSTALLATION ...
Страница 17: ...INSTALLATION 2 5 ...
Страница 21: ...INSTALLATION ...
Страница 32: ...OPERATION Figure 3 2 BMS II Menu Structure 3 4 ...
Страница 46: ......
Страница 64: ......
Страница 70: ......
Страница 72: ......
Страница 73: ...APPENDIX E E 1 APPENDIX E _____________________________ BMS II WIRING DIAGRAM ...
Страница 74: ......
Страница 76: ......
Страница 84: ......
Страница 88: ...APPENDIX H H 4 A _ ...
Страница 98: ......