Benchmark 2.0 LN Installation, Operation & Maintenance Manual
CHAPTER 7 – MAINTENANCE
Page
86
of
168
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0046_0J
06/18/2015
Phone: 800-526-0288
GF-123
IGNITOR-
INJECTOR
3/8-16
NUTS (8)
BLOWER
BURNER
PLATE
AIR/FUEL
VALVE
FLAME
DETECTOR
STAGED
IGNITION
ASSEMBLY
1/2” BOLTS & NUTS (4)
CONNECT AIR/FUEL VALVE
TO GAS TRAIN
GROUNDING
SCREW
(10-32 x 1/2" LG.)
Figure 7-4: Burner Assembly Mounting Details
4. Remove the two (2) screws securing the flame detector to the plate. The flame detector is
secured to the burner plate with one (1) #10-32 screw and one (1) #8-32 screw.
5. Remove the flame detector and gasket from the burner plate.
6. Disconnect the cable from the igniter.
7. Using a 7/16” open-end wrench, disconnect the compression nut securing the gas injector
tube of the igniter to the elbow of the staged ignition assembly (see Figure 7-2).
Disconnect the staged ignition assembly from the igniter.
IMPORTANT
Prior to removing the igniter, note the position of the gas injector tube
relative to the burner plate and blower. This is necessary to ensure that the
igniter injector is reinstalled in the proper orientation when it is reconnected
to the staged ignition assembly.
8. Next, loosen and remove the igniter from the burner plate using a 1" open-end wrench.
9. Disconnect the unit wiring harness connectors from the air/fuel valve and blower motor.
10. Disconnect the wire leads connected to the blower proof switch and blocked inlet switch
(Figure 7-5).
11. Remove the 10-32 x 1/2" long grounding screw from the burner plate (Figure 7-4).
12. Disconnect the gas train from the air/fuel valve by removing the four (4) 1/2” bolts and
nuts (Figure 7-4).
13. Disconnect the inlet air flex hose from the air/fuel valve by loosening the hose clamp.