Benchmark 2.0 LN Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
Page
42
of
168
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0046_0J
06/18/2015
Phone: 800-526-0288
GF-123
3.6 CONFIGURATION MENU
The Configuration Menu shown in Table 3-4 permits adjustment of the Internal Setpoint (Setpt)
temperature regardless of whether the valid password has been entered. Setpt is required for
operation in the Constant Setpoint mode. The remaining options in this menu require the valid
password to be entered, prior to changing existing entries. This menu contains a number of other
configuration settings which may or may not be displayed, depending on the current operating
mode setting.
NOTE
The Configuration Menu settings shown in Table 3-4 are Factory-Set in
accordance with the requirements specified for each individual order.
Therefore, under normal operating conditions, no changes will be required.
Table 3-4. Configuration Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Internal Setpt
Lo Temp
Limit
Hi Temp Limit 130°F
Unit Type
KC Boiler, KC Boiler LN,
BMK Boiler Std, BMK Boiler
LN, BMK Boiler Dual,
KC Water Heater, KC Wtr
Heater LN, Innovation WH
BMK Boiler
LN
Unit Size
(See
NOTE
at end
of Table 3-4)
750 MBH, 1000 MBH, 1500
MBH, 2000 MBH, 3000 MBH
2000 MBH
(2.0 MBTU)
Fuel Type
Natural Gas, Propane
Natural Gas
Boiler Mode
Constant Setpoint,
Remote Setpoint,
Direct Drive
Combination
Outdoor Reset
Constant
Setpoint
Remote Signal
(If Mode = Remote
Setpoint, Direct
Drive or
Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (BMS)
Network
4 – 20 mA,
1-5V
Bldg Ref Temp
(If Mode = Outdoor
Reset)
40°F
230°F
70°F
Reset Ratio
(If Mode = Outdoor
Reset)
0.1
9.9
1.2
Outdoor Sensor
Enabled or Disabled
Disabled
System Start Tmp
(If Outdoor Sensor
= Enabled)
30°F
100°F
60°F