Benchmark 2.0 LN Installation, Operation & Maintenance Manual
CHAPTER 8 – TROUBLESHOOTING GUIDE
Page
102
of
168
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0046_0J
06/18/2015
Phone: 800-526-0288
GF-123
TABLE 8-1. BOILER TROUBLESHOOTING
(Continued)
FAULT INDICATION
PROBABLE CAUSES
CORRECTIVE ACTION
RESIDUAL
FLAME
1.
SSOV not fully closed.
2.
Defective Flame Detector
1.
Check open/close indicator window of Safety Shut-Off Valve
(SSOV) and ensure that the SSOV is fully closed. If not fully
closed, replace the valve and or actuator.
Close gas shut-off valve downstream of SSOV. Install a
manometer or gauge in a gas test port between the SSOV and
the gas shut off valve. If a gas pressure reading is observed
replace the SSOV valve and or actuator.2.
2.
Replace Flame Detector.
SSOV FAULT
DURING PURGE
See SSOV SWITCH OPEN
SSOV FAULT
DURING RUN
1.
SSOV switch closed for 15 seconds
during run.
1.
Replace or adjust microswitch in SSOV actuator. If fault
persists, replace actuator.
SSOV RELAY
FAILURE
1.
SSOV relay failed on board.
2.
Floating Neutral.
3.
Hot and Neutral reversed at SSOV.
1.
Press CLEAR button and restart unit. If fault persists, replace
Ignition/Stepper (IGST) Board.
2.
The Neutral and Earth Ground are not connected at the source
and therefore there is a voltage measured between the two.
Normally this measurement should be near zero or no more
than a few millivolts.
3.
Check SSOV power wiring.
SSOV
SWITCH OPEN
1.
Actuator not allowing for full closure
of gas valve
2.
SSOV powered when it should not
be
3.
Defective Switch or Actuator
4.
Incorrectly wire switch
1.
Observe operation of the Safety Shut-Off Valve (SSOV)
through indicator on the Valve actuator and ensure that the
valve is fully and not partially closing.
2.
If the SSOV never closes, it may be powered continuously.
Close the gas supply and remove power from the unit. Refer
fault to qualified service personnel.
3.
Remove the electrical cover from the SSOV and check switch
continuity. If the switch does not show continuity with the gas
valve closed, either adjust or replace the switch or actuator.
4.
Ensure that the SSOV Proof of Closure switch is correctly
wired.