Benchmark 2.0 LN Installation, Operation & Maintenance Manual
CHAPTER 4 – INITIAL START-UP
OMM-0046_0J
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
57
of
168
GF-123
Ph.: 800-526-0288
06/18/2015
Table 4-3: Combustion Oxygen Levels for a
60%
Air/Fuel Valve Position
Oxygen %
± 0.2
Carbon Monoxide
NOx
5.7 %
<50 ppm
<30 ppm
32.
If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.
33. Once the oxygen level is within the specified range at 60%, press the
ENTER
key to store
the selected blower output voltage for the 60% valve position.
34.
Press the ▲ arrow key until
SET Valve Position
appears on the C-MORE display.
35. Press the
CHANGE
key.
SET Valve Position
will begin to flash.
36.
Press the ▼ arrow key until the
SET Valve Position
reads
45%
, then press the
ENTER
key.
37.
Press the ▼ arrow key until
CAL Voltage 45%
is displayed.
38. Press the
CHANGE
key.
CAL Voltage 45%
will begin to flash.
39. The oxygen level at the 45% valve position should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.
Table 4-4: Combustion Oxygen Levels for a
45%
Air/Fuel Valve Position
Oxygen %
± 0.2
Carbon Monoxide NOx
7.2 %
<50 ppm
<30 ppm
40.
If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.
41. Once the oxygen level is within the specified range at 45%, press the
ENTER
key to store
the selected blower output voltage for the 45% valve position.
42.
Press the ▲ arrow key until
SET Valve Position
appears on the C-MORE display.
43. Press the
CHANGE
key.
SET Valve Position
will begin to flash.
44.
Press the ▼ arrow key until the
SET Valve Position
reads
30%
, then press the
ENTER
key.
45.
Press the ▼ arrow key until
CAL Voltage 30%
is displayed.
46. Press the
CHANGE
key.
CAL Voltage 30%
will begin to flash.
47. The oxygen level at the 30% valve position should be as shown in Table 4-5. Also, ensure
that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the
values shown.
Table 4-5: Combustion Oxygen Levels for a
30%
Air/Fuel Valve Position
Oxygen %
± 0.2
Carbon Monoxide NOx
8.0 %
<50 ppm
<30 ppm