PD201808 AEG GRID-TIED THREE-PHASE SOLAR INVERTER (12-30 kW) V.2-18 EN
40
Setting item
LCD display
Instruction
Run Param
Run Param
UV Volt
UV time
OV Volt
OV time
UF Freq
UF time
ACUV Volt(phase volt)
184V
ACUV Time
0.20s
ACOV Volt(phase volt)
263V
ACOV Time
0.20s
ACUF Freqency
47.6Hz
ACUF Time
0.20s
ACOF Freqency
51.4Hz
ACOF Time
0.20s
Input password
0000
Accessing the “Run Param” interface requires a password.
You can obtain the password from your supplier if neces-
sary. Set ACUV Volt, ACUV time etc. under the related sub-
menus, press “ ” and “ ” to modify, and press “ENT” to
confirm.