3.2.3 Connection cables
Compatibly with the AEG inverter´s AC/DC connector specifications for different inverter models, below is an overview of the
cable specifications:
Model
DC side
AC side
Min.cross-section
area mm² (length
≤50m) mm
²
Min.cross-section
area mm²
(length >50m)
Min. cross-section
area mm²
(length ≤50m)
L
N/PE
AS-IC01-12000-2 / AS-IC01-15000-2 /
AS-IC01-17000-2
4
6
6
4
AS-IC01-20000-2 / AS-IC01-25000-2 /
4
6
8
4
AS-IC01-30000-2
4
6
10
6
Table 9: Cable specifications
3.2.4 Miniature circuit breakers
In order to ensure safe operation of the inverter and circuits, it is recommender to place micro breakers or
fuses on the DC input end and on the AC output end of the inverter.
The wiring shall follow local electric codes. Choose proper cables for power input and output lines.
Input and output cables shall be solar cables suitable for outdoor use.
The below table reports the recommended specifications for the micro breakers:
Model
DC input
AC output
Recommended DC breakers
(optional for length >100m)
Recommended AC breakers
AS-IC01-12000-2
DC1000V, C32A, 2P
AC400V, C25A, 4P
AS-IC01-15000-2
DC1000V, C32A, 2P
AC400V, C32A, 4P
AS-IC01-17000-2
DC1000V, C32A, 2P
AC400V, C35A, 4P
AS-IC01-20000-2
DC1000V, C40A, 2P
AC400V, C50A, 4P
AS-IC01-25000-2
DC1000V, C40A, 2P
AC400V, C63A, 4P
AS-IC01-30000-2
DC1000V, C50A, 2P
AC400V, C63A, 4P
Table 10: Breaker specifications