PD201808 AEG GRID-TIED THREE-PHASE SOLAR INVERTER (12-30 kW) V.2-18 EN
39
Setting item
LCD display
Instruction
Set power
set power
P-Lmt
Mode
LmtPower
P.Factor
Limit Mode
:
Invalid
Invalid
Auto
Manual
Limit Power
100%
Power Factor
Grid Tied Mode
Normal Mode
Power Factor
:
1.00
Input password
0000
Accessing the “Set power” interface requires a password.
You can request it from your supplier if necessary.
The Set power interface of AEG inverters features 3 sub-
menus as below.
AEG three-phase inverters only feature
submenu nr.
③
:
①
P-Lmt Mode: invalid (limited power function is invalid),
auto (
special for single-phase
), manual (set the limit of out-
put value manually);
②
LmtPower: this function is only valid when the P-Lmt
Mode is manual, the percentage is that of the rated power
and the setting range is from 10% to 100%;
③
p.Factor: includes normal model (default value “1”), cur-
rent advanced mode and current hysteresis mode and the
setting rage is -0.9-0.99.
Personal
Personal
MPP Start Volt
MPPT Volt
120V
Input password
0000
This function is only valid for single-phase inverters.
Accessing the “Personal” interface requires a password.
You can obtain the password from your supplier if neces-
sary. The MPPT starting voltage can be set in this menu
from 120V to 160V under the submenu of ”MPPT start
volt”.