51
5.3 TEST MODE
Test Mode is used when testing the fire alarm system. In test mode the devices in the zone(s) in test, detectors
and call points etc, can be activated and the panel will automatically reset, enabling the system to be tested by
one person. It is possible to test head removal monitoring and to test the system with or without the sounders.
To initialise Test Mode, firstly activate the controls by turning the key
switch or by entering the four digit code. Then press and hold the Test
Mode button (2) for 3 seconds.
After 3 seconds the panel will bleep and the Test Mode LED and Zone 1
Fault/Disabled/Test LED will pulse slowly, indicating that Zone 1 is in test
selection mode. The Sounder Status LED will also be pulsing rapidly; this
indicates that the test will be
with
sounders. (Test mode without
sounders is explained below)
Pressing the Test Mode button again will move test selection mode to Zone 2 and the Zone 2
Fault/Disabled/Test LED will be pulsing instead. Subsequent presses will move the selection to Zones 3 - 12,
dependant on the number of zones fitted to the panel. I.e up to zone 4 on a 4 zone, 6 on a 6 zone, 8 on a
8 zone etc.
After the last available zone the next press will move the selection mode to the sounder circuits, indicated by no
Zone Fault/Disabled/Test LEDs on. This position selects whether or not the sounders will ring during test.
Pressing the button once more will move the selection back to Zone 1 again.
When the desired zone to be tested is indicated by a slow pulsing LED,
use the ENTER button to select it. Once selected the indicator LED will
change to a rapid pulse. Pressing ENTER again will toggle the zone
between in and out of test. Then use Test Mode button again to move
to the next zone. Any or all zones can be in test mode simultaneously.
When at the sounder status position, use the ENTER button to toggle
between testing with or without sounders. A rapid pulse = with
sounders (default), a slow pulse = without sounders.
When all zones to be tested have been set, press and hold the Test Mode button for 3 seconds again. This will
exit the test selection mode. All zones in test and the Test Mode will now be indicated by a steady LED.
To take zones out of test mode, repeat the above process using the Test Mode button to select the zone and
the ENTER button to change the status.
Test Mode
“With” Sounders
Activation of a call point or detector - sounders will pulse twice, device is automatically reset.
Removal of a detector - sounders will pulse once.
Test Mode
“Without” Sounders
Activation of a call point or detector - panel buzzer and LED response only, device is automatically reset.
Tip:
With the controls active, pressing the Test Mode button briefly will reveal which circuits are in test mode (as
opposed to disabled). This is useful if using Disable Mode and Test Mode at the same time.
www.acornfiresecurity.com
www.acornfiresecurity.com
Содержание Quick Zone XL
Страница 5: ...5 1 2 CABINET DETAILS www acornfiresecurity com www acornfiresecurity com...
Страница 8: ...8 1 4 MAIN PCB TERMINALS www acornfiresecurity com www acornfiresecurity com...
Страница 14: ...14 2 2 GENERAL CONVENTIONAL SYSTEM SCHEMATIC www acornfiresecurity com www acornfiresecurity com...
Страница 15: ...15 2 3 GENERAL TWIN WIRE SYSTEM SCHEMATIC www acornfiresecurity com www acornfiresecurity com...
Страница 66: ...66 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com...
Страница 67: ...USER NOTES www acornfiresecurity com www acornfiresecurity com...
Страница 68: ...www acornfiresecurity com www acornfiresecurity com...