33
Dependency Mode Selection
To change the dependency mode type for the panel, enter the above code and press ENTER (panel is set to
type A by default).
The amber, fault / disabled / test LED 1 will pulse and the current setting will be indicated by a steady amber,
fault / disabled / test LED as per table below.
LED 1
LED 2
LED 3
LED 4
No Dependency Mode
Type A
Type B
Type C
Use button 1 to move the pulsing amber LED to the required type as per above and press ENTER to select it.
The LED will change to a rapid pulse to indicate that it is now the current setting.
Press and hold button 1 for 3 seconds to save the setting and exit the programming mode.
Select Zones for Dependency Mode
To select which zones should be included in the dependency mode, enter the above code and press ENTER.
The amber, fault / disabled / test LED 1 will pulse and any zones that are currently set to dependency mode will
be indicated by a steady amber, fault / disabled / test LED.
Use button 1 to move the pulsing amber LED to the required zone(s) for setting and press ENTER to select.
The LED will change to a rapid pulse to indicate that the zone is now set to dependency mode. Pressing
ENTER again will de-select the zone and the LED will change back to a slow pulse.
Press and hold button 1 for 3 seconds to save the settings and exit the programming mode.
Set Timings for Dependency Mode B
There are two programmable timings for dependency mode B, the confirmation time
1
, and the auto reset time
2
.
Enter the above code and press ENTER. The fire LED 1 will light indicating changing the timing for the
confirmation time, 1 - 4 minutes. Use button 1 to move to fire LED 2, for changing the timing for the auto reset
time (5 - 30 minutes). A third press of button 1 will light fire LED 3 which is for changing Twin Wire detector
compatibility (see over page), and then back to 1 again.
With the required fire LED lit, the amber, fault / disabled / test LEDs will indicate the current timings set. Press
the ENTER button to enter ‘edit mode’ and the fire LED will change to pulsing.
Now use buttons 1 & 3 to increase or decrease the time. Button 1 increases, button 3 decreases. When finished
press ENTER again to return to ‘view mode’
The confirmation time 1 is indicated by the amber, fault / disabled / test LEDs 1 - 4 (1 - 4 minutes).
The auto reset time 2 is indicated by the amber, fault / disabled / test LEDs 1 - 5 using binary code values.
See table below. Each push will increase or decrease the time by 1 minute.
AMBER LED 1
AMBER LED 2
AMBER LED 3
AMBER LED 4
AMBER LED 5
1 Minute
2 Minutes
4 Minutes
8 Minutes
16 Minutes
www.acornfiresecurity.com
www.acornfiresecurity.com
Содержание Quick Zone XL
Страница 5: ...5 1 2 CABINET DETAILS www acornfiresecurity com www acornfiresecurity com...
Страница 8: ...8 1 4 MAIN PCB TERMINALS www acornfiresecurity com www acornfiresecurity com...
Страница 14: ...14 2 2 GENERAL CONVENTIONAL SYSTEM SCHEMATIC www acornfiresecurity com www acornfiresecurity com...
Страница 15: ...15 2 3 GENERAL TWIN WIRE SYSTEM SCHEMATIC www acornfiresecurity com www acornfiresecurity com...
Страница 66: ...66 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com...
Страница 67: ...USER NOTES www acornfiresecurity com www acornfiresecurity com...
Страница 68: ...www acornfiresecurity com www acornfiresecurity com...