7.8.2.3 Disable - Controls
Disabling Controls will cancel any Level 2 or above access User Level and return the panel to a Level 1 access
level. Access Level 1 requires an access password for any control button (i.e.: ACK, RESET, etc.) or keypad entry
usage.
Note: If the panel has an optional access Level key switch installed, the installer needs to program for
disabled controls so the key switch will be the only means for access to control button and keypad usage.
Press the
buttons to highlight the Controls option and then press the
✔
button to select it.
If the current User ID (access level password) does not have the required authority, the display prompts for entry of
an authorized password to guard against inadvertent changes.
Once a valid access password has been entered, the control button functions and menu functions are disabled and
the level 1 menu display will be shown:
[ CONTROLS DISABLED ]
ENABLE CONTROLS
VIEW
LED TEST STATUS
The display will automatically revert to the normal operating display after 15 seconds.
7.8.2.4 Disable – User ID
If User-ID access is programmed by the PC-NeT field configuration program, this operation will cancel the current
User ID access and return to the Default User Level 1 access. User Level 1 can perform all actions except those
defined as programmable (refer to the menu table).
[Disable] User 5 Node 1
ZONE/INPUTS OUTPUTS GROUPS
CONTROLS
USER-ID
Press the
buttons to highlight the User-ID option and then press the
✔
button to select it.
[Disable] User 1 Node 1
ZONE/INPUTS OUTPUTS GROUPS
CONTROLS
USER-ID
NOTE: If configured to operate with a timeout and if there has been no user activity (button pressed) after
the programmable time period (default “No Timeout”), the panel will automatically cancel a User ID level
access and return the panel to User 1 ID access level. This is to ensure that access to restricted options,
are automatically cancelled.
[Disable] User 1 Node 1
ZONE/INPUTS OUTPUTS GROUPS
CONTROLS
USER-ID