![Advanced Axis AX-CTL-1L Скачать руководство пользователя страница 110](http://html1.mh-extra.com/html/advanced/axis-ax-ctl-1l/axis-ax-ctl-1l_installation-and-operation-manual_2855749110.webp)
www.advancedco.com
110
10.1.1 AX-CTL Base Card I/O Addresses and Built-in Intelligent Multi-Meter
The following is a list of AX-CTL base card addresses for troubleshooting various input and output circuits:
Item
(Address)
Description
Value
(Real-Time) State
01.0
NAC-1 A Volts
(Voltage)*
(State of Output Voltage)
01.1
NAC-2 A Volts
(Voltage)
(State of Output Voltage)
01.2
NAC-3 A Volts
(Voltage)
(State of Output Voltage)
01.3
NAC-4 A Volts
(Voltage)
(State of Output Voltage)
* ~5.5V quiescent and ~ 27V alarm = Normal
If system has only 2 NACs quiescent and alarm voltages for NAC-3 & NAC-4 = 0V
02.0
NAC-1 A Load
(Current)*
(State of Output Current)
02.1
NAC-2 A Load
(Current)
(State of Output Current)
02.2
NAC-3 A Load
(Current)
(State of Output Current)
02.3
NAC-4 A Load
(Current)
(State of Output Current)
* Dependent upon quiescent and alarm current draw of notification appliances per circuit
If only 2 NAC circuits per system quiescent and alarm currents for NAC-3 & NAC-4 = 0mA
03.0
Battery
(~27V
=
Normal) (State of Battery Voltage)
04.0
Charger (V)
(~27V = Normal) (State of Charger Voltage)
04.1
Charger (I)
(Current)*
(State of Charger Current)
* Dependent upon whether batteries are being charged, 0mA if no charge needed
04.2
Charger
(C)
(~25
0
C = Normal)
(State of Charger Temp. in
0
C)
05.0
Ground Volts
(~13V = Normal)* (State of Ground Voltage)
* Higher voltage = positive ground, lower voltage = negative ground (voltage dependent upon ground potential)
05.1
System Volts
(~27V = Normal) (State of System Voltage)
06.0
Aux Supply 1
(Current)*
(State of Aux 1 Output Current)
06.1
Aux Supply 2
(Current)*
(State of Aux 2 Output Current)
* Dependent upon current draw of auxiliary supply output
07.0
1
st
SLC Load
(Current)*
(State of 1
st
SLC Loop Current)
07.1
2
nd
SLC Load
(Current)
(State of 2
nd
SLC Loop Current)
07.2
3
rd
SLC Load
(Current)
(State of 3
rd
SLC Loop Current)
07.3
4
th
SLC Load
(Current)
(State of 4
th
SLC Loop Current)
* Dependent upon quiescent and alarm current draw of SLC devices per loop
08.0
1
st
SLC V. Out
(~23V = Normal)* (State of 1
st
SLC Loop Voltage Out)
08.1
2
nd
SLC V. Out
(~23V = Normal)* (State of 2
nd
SLC Loop Voltage Out)
08.2
3
rd
SLC V. Out
(~23V = Normal)* (State of 3
rd
SLC Loop Voltage Out)
08.3
4
th
SLC V. Out
(~23V = Normal)* (State of 4
th
SLC Loop Voltage Out)
* If system has only 2 SLCs voltage for SLC-3 & SLC- 4 = 0V, and State is RESET
09.0
1
st
SLC V. In
(~23V = Normal)* (State of 1
st
SLC Loop Voltage In)
09.1
2
nd
SLC V. In
(~23V = Normal)* (State of 2
nd
SLC Loop Voltage In)
09.2
3
rd
SLC V. In
(~23V = Normal)* (State of 3
rd
SLC Loop Voltage In)
09.3
4
th
SLC V. In
(~23V = Normal)* (State of 4
th
SLC Loop Voltage In)
* 0V if Class B, if Class A and only 2 SLCs voltage for SLC-3 & SLC- 4 = 0V
at 0V State is RESET
10.0
1
st
Switch Input (LCD)
L*
(State of Control Circuitry)*
10.1
2
nd
Switch Input (LCD)
L
(State of Control Circuitry)
10.2
3
rd
Switch Input (LCD)
L
(State of Control Circuitry)
10.3
4
th
Switch Input (LCD)
L
(State of Control Circuitry)
10.4
5
th
Switch Input (LCD)
L
(State of Control Circuitry)
10.5
6
th
Switch Input (LCD)
L
(State of Control Circuitry)
10.6
7
th
Switch Input (LCD)
L
(State of Control Circuitry)
10.7
8
th
Switch Input (LCD)
L
(State of Control Circuitry)
* Normal Low (L – open contact), Active High (H – closed contact)
State only changes on circuitry failure
11.0
Relay
1
-*
(State
of
Relay
Circuitry)*
11.1
Relay
2
- (State
of
Relay
Circuitry)
11.2
Relay
3
- (State
of
Relay
Circuitry)
11.3
Output
1
- (State
of
Relay
Circuitry)
11.4
Output
2
- (State
of
Relay
Circuitry)
11.5
Output
3
- (State
of
Relay
Circuitry)
11.6
Output
4
- (State
of
Relay
Circuitry)
11.7
Output
5
- (State
of
Relay
Circuitry)
11.8
Output
6
- (State
of
Relay
Circuitry)
11.9
Output
7
- (State
of
Relay
Circuitry)
11.10
Output
8
- (State
of
Relay
Circuitry)
* - = No voltage or current readings, dry contact
State normally equals RESET it only changes on circuitry failure