If SELECTED INPUTS is chosen, the pop-up window disappears and a list of the input devices within the selected
zone is presented. For example:
[ Inputs in Zone 0001] More>
Mode Device Text
Enabled
BASEMENT WEST
Disabled BASEMENT EAST
Enabled GROUND FLOOR
Enabled MAIN RECEPTION AREA
Press the
button for more information on the inputs, including loop number, address, device type, analog value,
etc.
Press the
buttons to scroll through and highlight the required input and then press the
✔
button to disable it.
Pressing the
✔
button when the input is already disabled will enable the input.
Press the “Esc”
button
to return.
If ONLY AUTOMATIC DETECTORS is chosen, the pop-up window disappears and all detectors within the zone will
be disabled and the Zone Mode status will change from “Enabled” to “PART DISABLED”.
If ONLY MANUAL DEVICES chosen, the pop-up window disappears and all manual pull stations within the zone will
be disabled and the Zone Mode status will change from “Enabled” to “PART DISABLED”. If there are no pull
stations within the zone nothing will be disabled.
If ALL OTHER DEVICES chosen, the pop-up window disappears and all none alarm, none mass notification, none
supervisory points (including firefighter phones) within the zone will be disabled and the Zone Mode status will
change from “Enabled” to “PART DISABLED”.
7.8.2.2 Disable - Outputs
The Disable Outputs Option allows for the isolation of some or all of the outputs. If disabled, the outputs will not
activate in the event of an alarm or other programmed event.
If the current User ID (access level password) does not have the required authority, the display prompts for entry of
an authorized password to guard against inadvertent changes.
Once a valid access password has been entered, a pop-up window is shown on the display to select the type of
outputs to disable. Scroll down to view / select the available options.
ALL OUTPUTS
.
NACS
RELAYS
ONLY SELECTED OUTPUTS
Note: “Strobes” can be added to the disable outputs pop-up window via the PC-NeT field configuration
programming tool, under “Disable Outputs Menu Options”.
7.8.2.2.1 All Outputs
On access to the “Disable – Outputs” menu the “ALL OUTPUTS” will be highlighted and then pressing the
✔
button
will disable all outputs. The display automatically reverts to the Main Disable Menu and the ‘NAC Disabled’ LED will
illuminate, indicating NACs disabled.
ALL OUTPUTS
.
NACS
RELAYS
ONLY SELECTED OUTPUTS
Note: On networked systems this only disables the outputs connected to this panel. In addition, it will
disable all NAC type outputs.