7 Operation
7.1 User Controls and Indications
7.1.1 Control Keys
RESET
Press to reset the panel from a latched alarm (or other programmed latched input i.e.
latching trouble or supervisory condition) or press to deactivate a Drill condition.
ACKNOWLEDGE
Press to acknowledge an alarm, supervisory and/or trouble condition. LED indications on
the panel change from flashing to steady and zone/device display removes the word
“New”.
Note: All current conditions are simultaneously acknowledged “Global
Acknowledgement”.
RESOUND ALARMS
Press to reactivate any silenced notification appliances connected to system NAC circuits
or any output module of an SLC circuit programmed as “Silenceable”.
SILENCE ALARMS
Press to silence active notification appliances connected to system NAC circuits or any
output module of an SLC circuit programmed as “Silenceable”.
DRILL
(HOLD 2 SECONDS)
Press and hold for 2 seconds to activate a Drill condition. All notification appliance circuits
programmed to activate on Drill will be activated. Press and hold for 2 seconds to
deactivate a drill condition.
FUNCTION KEYS F1, F2, F3
Programmable control buttons.