V6.230 20131017
55
Enter:59/4.0
This will program LSP11 pickup to 4.0A.
Enter:60/3.5
This will program LSP11 drop out to 3.5A.
NOTE: Load pickup and drop out set points are the CT bushing secondary
current and must always be entered with a decimal point and trailing 1/10’s
digit. For 3 amps you must enter 3.0. For .5 amps you must enter 0.5.
4.7.2 Setting Load Pickup Timer
Programming Load Pickup Timer for the above illustrated Load Set Point 11 from
the front panel, press the
or
arrow buttons until the setting 095 is displayed:
Press the
YES
button. The first digit will flash. Use the
or
arrow buttons to
scroll through the digits 0 – 9. Use the
or
buttons to scroll between the
digits. The currently active digit will flash. Press
YES
after you have entered all
digits.
The Pickup Timer for the other load set points can be changed by pressing the
arrow button to the corresponding Load Pickup Timer and following the above
procedure.
For programming from a PC just type the load set point pickup timer value on the
“Enter:” line as follows:
Enter:95/120
This will program the Load pickup timer to 120 seconds.
4.8
Optically Isolated Input Settings
The TTC-1000 may be optionally equipped with up to 14 optically isolated inputs.
Each input contains a limiting resistor that allows these inputs to recognize a
wide range of input voltage of 38 to 160 Volts AC or DC as being picked up.
Inputs 1 and 2 are scanned every 32 milliseconds. Inputs 3 through 14 are
scanned slightly less frequently. Every input’s contact chatter is debounced by
requiring the input be stable for two scans before the new state is recognized.
Inputs may be assigned to any output using the programmable logic.
PRGM SETTING 095
LSP11PUTMR=120sec
Содержание TTC-1000
Страница 11: ...Warranty V6 230 20131017 x PAGE INTENTIONALLY BLANK ...
Страница 41: ...V6 230 20131017 30 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 121: ...V6 230 20131017 110 PAGE INTENTIONALLY BLANK ...
Страница 133: ...V6 230 20131017 122 PAGE INTENTIONALLY BLANK ...
Страница 152: ...V6 230 20131017 141 6 After closing the import wizard the text data will display The data is now ready for graphing ...
Страница 153: ...V6 230 20131017 142 PAGE INTENTIONALLY BLANK ...
Страница 157: ...V6 230 20131017 146 PAGE INTENTIONALLY BLANK ...
Страница 199: ...V6 230 20131017 188 PAGE INTENTIONALLY BLANK ...
Страница 247: ...V6 230 20131017 236 PAGE INTENTIONALLY LEFT BLANK ...